Honeywell
• 41
HVAC A
PPLICATION
Table 27. Digital input settings
M3.5.1.23
PID1 select setpoint
DigIN Slot0.1 1046
FALSE = Setpoint 1
TRUE = Setpoint 2
M3.5.1.24
PID2 start signal
DigIN Slot0.2 1049
FALSE = PID2 in stop mode
TRUE = PID2 regulating
This parameter will have no effect if PID2 con-
troller is not enabled in the Basic menu for
PID2
M3.5.1.25
PID2 select setpoint
DigIN Slot0.1 1048
FALSE = Setpoint 1
TRUE = Setpoint 2
M3.5.1.26
Motor 1 interlock
DigIN Slot0.1
426
FALSE = Not active
TRUE = Active
M3.5.1.27
Motor 2 interlock
DigIN Slot0.1
427
FALSE = Not active
TRUE = Active
M3.5.1.28
Motor 3 interlock
DigIN Slot0.1
428
FALSE = Not active
TRUE = Active
M3.5.1.29
Motor 4 interlock
DigIN Slot0.1
429
FALSE = Not active
TRUE = Active
M3.5.1.30
Motor potentiometer UP
DigIN Slot0.1
418
FALSE = Not active
TRUE = Active (Motor potentiometer refer-
ence INCREASES until the contact is opened)
M3.5.1.31
Motor potentiometer
DOWN
DigIN Slot0.1
417
FALSE = Not active
TRUE = Active (Motor potentiometer refer-
ence DECREASES until the contact is
opened)
M3.5.1.32
Reset Maintenance
counter 1
DigIN Slot0.1
490 TRUE = Reset
M3.5.1.33
Reset Maintenance
counter 2
DigIN Slot0.1
491 TRUE = Reset
M3.5.1.34
Reset Maintenance
counter 3
DigIN Slot0.1
492 TRUE = Reset
Содержание SmartVFD HVAC MR4
Страница 7: ...Honeywell 5 SAFETY ...
Страница 49: ...Honeywell 47 COMMISSIONING ...
Страница 78: ...STARTUP Honeywell 6 ...