HVAC A
PPLICATION
Honeywell
• 70
M3.5.2.2
AI1
SIGNAL
FILTER
TIME
When this parameter is given a value greater than 0 the function that filters out disturbances
from the incoming analog signal is activated.
NOTE: Long filtering time makes the regulation response slower!
Figure 12. AI1 signal filtering
M3.5.3.2.1
B
ASIC
RO1
FUNCTION
Selection
Selection name
Description
0
Not used
1
Ready
The drive is ready to operate
2
Run
The drive operates (motor is running)
3
General fault
A fault trip has occurred
4
General fault inverted
A fault trip has
not
occurred
5
General alarm
6
Reversed
The reverse command has been selected
7
At speed
The output frequency has reached the set reference
8
Motor regulator activated
One of the limit regulators (e.g. current limit, torque limit)
is activated
9
Preset frequency active
The preset
frequency
has been selected with digital input
10
Keypad control active
Keypad control mode selected
11
I/O control B active
I/O control place B selected
12
Limit supervision 1
Activates if the signal value falls below or exceeds the set
supervision limit (M3.8.3 or M3.8.7) depending on the
selected function.
13
Limit supervision 2
14
Start command active
Start command is active.
15
Reserved
16
Fire mode ON
17
RTC timer 1 control
Time channel 1 is used.
%
100%
63%
M3.5.2.2
t [s]
1100 K11
Filtered signal
Unfiltered signal