HVAC A
PPLICATION
Honeywell
• 40
3.5.7
Group 3.5: I/O Configuration
3.5.7.1
Digital inputs
Digital inputs are very flexible to use. Parameters are functions that are connected to the re-
quired digital input terminal. The digital inputs are represented as, for example,
DigIN Slot A.2,
meaning the second input on slot A.
It's also possible to connect the digital inputs to time channels which are also represented as
terminals.
Code
Parameter
Default
ID
Description
M3.5.1.1
Control signal 1 A
DigIN SlotA.1
403
Start signal 1 when control place is I/O 1
(FWD)
M3.5.1.2
Control signal 2 A
DigIN Slot0.1
404
Start signal 2 when control place is I/O 1
(REV)
M3.5.1.3
Control signal 1 B
DigIN Slot0.1
423 Start signal 1 when control place is I/O B
M3.5.1.4
Control signal 2 B
DigIN Slot0.1
424 Start signal 2 when control place is I/O B
M3.5.1.5
I/O B control force
DigIN Slot0.1
425 TRUE = Force the control place to I/O B
M3.5.1.6
I/O B reference force
DigIN Slot0.1
343
TRUE = Used frequency reference is speci-
fied by I/O reference B parameter (M3.3.4).
M3.5.1.7
External fault close
DigIN SlotA.3
405
FALSE = OK
TRUE = External fault
M3.5.1.8
External fault open
DigIN Slot0.2
406
FALSE = External fault
TRUE = OK
M3.5.1.9
Fault reset
DigIN SlotA.6
414 Resets all active faults
M3.5.1.10
Run enable
DigIN Slot0.2
407 Must be on to set drive in Ready state
M3.5.1.11
Run interlock 1
DigIN Slot0.1 1041
Drive may be ready but start is blocked as
long as interlock is on (Damper interlock).
M3.5.1.12
Run interlock 2
DigIN Slot0.1 1042 As above.
M3.5.1.13
Acceleration/Decelera-
tion time selection
DigIN Slot0.1
408
Used for switching between ramps 1 and 2.
FALSE=Ramp 1 shape, Acceleration time 1
and Deceleration time 1.
TRUE=Ramp 2 shape, Acceleration time 2
and Deceleration time 2.
M3.5.1.14
Motor preheat ON
DigIN Slot0.1 1044
FALSE = No action
TRUE = Uses the motor preheat DC-Current
in Stop state
Used when parameter M3.1.2.3 is set to 2.
M3.5.1.15
Fire Mode activation
DigIN Slot0.2 1596
FALSE = Fire Mode active
TRUE = No action
M3.5.1.16
Preset frequency selec-
tion 0
DigIN SlotA.4
419
Binary selector for Preset frequencies (0-7).
See page 37.
M3.5.1.17
Preset frequency selec-
tion 1
DigIN SlotA.5
420
Binary selector for Preset frequencies (0-7).
See page 37.
M3.5.1.18
Preset frequency selec-
tion 2
DigIN Slot0.1
421
Binary selector for Preset frequencies (0-7).
See page 37.
M3.5.1.19
Timer 1
DigIN Slot0.1
447
Rising edge starts Timer 1 programmed in
Group 3.11: Timer functions parameter group
M3.5.1.20
Timer 2
DigIN Slot0.1
448 See above
M3.5.1.21
Timer 3
DigIN Slot0.1
449 See above
M3.5.1.22
PID1 setpoint boost
DigIN Slot0.1 1047
FALSE = No boost
TRUE = Boost