HVAC A
PPLICATION
3.5.14.2
Setpoints
Code
Parameter
Min
Max
Unit
Default
ID
Description
M3.12.2.1
Keypad setpoint 1
Varies
Varies
Varies
0
167
M3.12.2.2
Keypad setpoint 2
Varies
Varies
Varies
0
168
M3.12.2.3
Setpoint ramp time
0.00
300.0
s
0.00
1068
Defines the rising and falling
ramp times for setpoint
changes. (Time to change
from minimum to maximum)
M3.12.2.4
Setpoint source 1
selection
0
16
1
332
0 = Not used
1 = Keypad setpoint 1
2 = Keypad setpoint 2
3 = AI1
4 = AI2
5 = AI3
6 = AI4
7 = AI5
8 = AI6
9 = ProcessDataIn1
10 = ProcessDataIn2
11 = ProcessDataIn3
12 = ProcessDataIn4
13 = ProcessDataIn5
14 = ProcessDataIn6
15 = ProcessDataIn7
16 = ProcessDataIn8
AI’s and ProcessDataIn are
handled as percent (0.00-
100.00%) and scaled accord-
ing to Setpoint minimum and
maximum.
NOTE:
ProcessDataIn use
two decimals.
M3.12.2.5
Setpoint 1 minimum
-200.00
200.00
%
0.00
1069
Minimum value at analog sig-
nal minimum.
M3.12.2.6
Setpoint 1 maximum
-200.00
200.00
%
100.00
1070
Maximum value at analog
signal maximum.
M3.12.2.7 Sleep frequency limit 1
0.00
320.00
Hz
0.00
1016
Drive goes to sleep mode
when the output frequency
stays below this limit for a
time greater than that defined
by parameter
Sleep delay
.
M3.12.2.8
Sleep delay 1
0
3000
s
0
1017
The minimum amount of time
the frequency has to remain
below the Sleep level before
the drive is stopped.
M3.12.2.9
Wake-up level 1
Varies
0.0000
1018
Defines the level for the PID
feedback value wake-up
supervision. Uses selected
process units.
M3.12.2.10
Setpoint 1 boost
-2.0
2.0
x
1.0
1071
The setpoint can be boosted
with a digital input.
M3.12.2.11
Setpoint source 2
selection
0
16
2
431 See par. M3.12.2.4
M3.12.2.12
Setpoint 2 minimum
-200.00
200.00
%
0.00
1073
Minimum value at analog sig-
nal minimum.