HVAC A
PPLICATION
Honeywell
• 76
M3.12.1.9
D
EAD
BAND
HYSTERESIS
M3.12.1.10
D
EAD
BAND
DELAY
The PID controller output is locked if the actual value stays within the deadband area around
the reference for a predefined time. This function will prevent unnecessary movement and wear
on actuators, e.g. valves.
Figure 17. Dead band
100K18.fh11
Dead band (M3.12.1.9)
Reference
Dead band delay (M3.12.1.10)
Output locked
Actual value
Содержание SmartVFD HVAC MR4
Страница 7: ...Honeywell 5 SAFETY ...
Страница 49: ...Honeywell 47 COMMISSIONING ...
Страница 78: ...STARTUP Honeywell 6 ...