Honeywell
• 53
HVAC A
PPLICATION
Table 38. Timer functions
M3.11.2.4
To day
0
6
0
1472 See Interval 1
M3.11.2.5 Assign to channel
0
3
0
1473 See Interval 1
3.11.3 INTERVAL 3
M3.11.3.1
ON time
00:00:00 23:59:59 hh:mm:ss 00:00:00 1474 See Interval 1
M3.11.3.2
OFF time
00:00:00 23:59:59 hh:mm:ss 00:00:00 1475 See Interval 1
M3.11.3.3
From day
0
6
0
1476 See Interval 1
M3.11.3.4
To day
0
6
0
1477 See Interval 1
M3.11.3.5 Assign to channel
0
3
0
1478 See Interval 1
3.11.4 INTERVAL 4
M3.11.4.1
ON time
00:00:00 23:59:59 hh:mm:ss 00:00:00 1479 See Interval 1
M3.11.4.2
OFF time
00:00:00 23:59:59 hh:mm:ss 00:00:00 1480 See Interval 1
M3.11.4.3
From day
0
6
0
1481 See Interval 1
M3.11.4.4
To day
0
6
0
1482 See Interval 1
M3.11.4.5 Assign to channel
0
3
0
1483 See Interval 1
3.11.5 INTERVAL 5
M3.11.5.1
ON time
00:00:00 23:59:59 hh:mm:ss 00:00:00 1484 See Interval 1
M3.11.5.2
OFF time
00:00:00 23:59:59 hh:mm:ss 00:00:00 1485 See Interval 1
M3.11.5.3
From day
0
6
0
1486 See Interval 1
M3.11.5.4
To day
0
6
0
1487 See Interval 1
M3.11.5.5 Assign to channel
0
3
0
1488 See Interval 1
3.11.6 TIMER 1
M3.11.6.1
Duration
0
72000
s
0
1489
The time the timer will run
when activated. (Activated by
DI)
M3.11.6.2 Assign to channel
0
3
0
1490
Select affected time channel
(1-3)
0=Not used
1=Time channel 1
2=Time channel 2
3=Time channel 3
3.11.7 TIMER 2
M3.11.7.1
Duration
0
72000
s
0
1491 See Timer 1
M3.11.7.2 Assign to channel
0
3
0
1492 See Timer 1
3.11.8 TIMER 3
M3.11.8.1
Duration
0
72000
s
0
1493 See Timer 1
M3.11.8.2 Assign to channel
0
3
0
1494 See Timer 1