3.5.16
Group 3.14: Pump and Fan Cascade
The
Multi-pump
functionality allows you to control
up to 4 motors
(pumps, fans) with PID con-
troller 1. The drive is connected to one motor which is the "regulating" motor connecting and
disconnecting the other motors to/from the mains, by means of contactors controlled with relays
when needed in order to maintain the right setpoint. The
Autochange
function controls the or-
der/priority in which the motors are started in order to guarantee their equal wear. The control-
ling motor
can be included
in the autochange and interlocks logic, or, it may be selected to
always functions as Motor 1. Motors can be taken out of use momentarily, e.g. for service, us-
ing the motor
Interlock function
. See page 82.
Table 50. Multi-pump parameters
Code
Parameter
Min
Max
Unit
Default
ID
Description
M3.14.1
Number of motors
1
4
1
1001
Total number of motors
(pumps/fans) used in multi-
pump system
M3.14.2
Interlock function
0
1
1
1032
Enable/Disable use of inter-
locks. Interlocks are used to
tell the system if a motor is
connected or not.
0 = Disabled
1 = Enabled
M3.14.3
Include FC
0
1
1
1028
Include the drive in the
autochange and interlocking
system.
0 = Disabled
1 = Enabled
M3.14.4
Autochange
0
1
0
1027
Disable/enable rotation of
starting order and priority of
motors.
0 = Disabled
1 = Enabled
M3.14.5
Autochange interval
0.0
3000.0
h
48.0
1029
After the expiry of the time
defined with this parameter,
the autochange function
takes place if the capacity
used lies below the level
defined with parameters
M3.14.6 and M3.14.7.
M3.14.6
Autochange: Fre-
quency limit
0.00
50.00
Hz
25.00
1031
These parameters define the
level below which the capac-
ity used must remain so that
the autochange can take
place.
M3.14.7
Autochange: Motor
limit
0
4
1
1030
M3.14.8
Bandwidth
0
100
%
10
1097
Percentage of the setpoint.
E.g.: Setpoint = 5 bar, Band-
width = 10%: As long as the
feedback value stays within
4.5...5.5 bar motor discon-
nection or removal will not
take place.
M3.14.9
Bandwidth delay
0
3600
s
10
1098
With feedback outside the
bandwidth, this time must
pass before pumps are
added or removed.