3.4
Monitor group
The drive provides you with a possibility to monitor the actual values of parameters and signals
as well as statuses and measurements. Some of the values to be monitored are customizable.
3.4.1
Multimonitor
On the multi-monitor page, you can collect nine values that you wish to monitor. See page 13
for more information.
3.4.2
Basic
See Table 14 in which the basic monitoring values are presented.
NOTE!
Only Basic I/O board statuses are available in the Monitor menu. Statuses for all I/O board
signals can be found as raw data in the I/O and Hardware system menu.
Check expander I/O board statuses when required in the I/O and Hardware system menu.
Monitoring value
Unit
ID
Description
M2.2.1
Output frequency
Hz
1
Output frequency to motor
M2.2.2 Frequency reference
Hz
25
Frequency reference to motor control
M2.2.3
Motor speed
rpm
2
Motor speed in rpm
M2.2.4
Motor current
A
3
M2.2.5
Motor torque
%
4
Calculated shaft torque
M2.2.7
Motor shaft power
%
5
Total power consumption of AC drive
M2.2.8
Motor shaft power
kW/hp
73
M2.2.9
Motor voltage
V
6
M2.2.10
DC link voltage
V
7
M2.2.11
Unit temperature
°C
8
Heatsink temperature
M2.2.12 Motor temperature
%
9
Calculated motor temperature
M2.2.13
Analog input 1
%
59
Signal in percent of used range
M2.2.14
Analog input 2
%
60
Signal in percent of used range
M2.2.15
Analog output 1
%
81
Signal in percent of used range
M2.2.16
Motor preheat
1228
0 = OFF
1 = Heating (feeding DC-current)
M2.2.17
Drive Status Word
43
Bit coded status of drive
B1=Ready
B2=Run
B3=Fault
B6=RunEnable
B7=AlarmActive
B10=DC Current in stop
B11=DC Brake Active
B12=RunRequest
B13=MotorRegulatorActive
M2.2.18
Last active fault
37
The fault code of latest activated fault
that has not been reset.