Honeywell
• 69
HVAC A
PPLICATION
NOTE:
The ramp time optimizer only affects the settings of Ramp 1. Ramp 2 will not be modi-
fied.
Figure 11.
M3.4.16
F
LUX
BRAKING
Instead of DC braking, flux braking is a useful way to raise the braking capacity in cases where
additional brake resistors are not needed.
When braking is needed, the frequency is reduced and the flux in the motor is increased, which
in turn increases the motor's capability to brake. Unlike DC braking, the motor speed remains
controlled during braking.
The flux braking can be set ON or OFF.
NOTE
: Flux braking converts the energy into heat at the motor, and should be used intermit-
tently to avoid motor damage.
M3.5.1.10
R
UN
ENABLE
Contact open: Start of motor
disabled
Contact closed: Start of motor
enabled
The drive is stopped according to the selected function at M3.2.5. The follower drive will always
coast to stop.
M3.5.1.11
R
UN
INTERLOCK
1
M3.5.1.12
R
UN
INTERLOCK
2
The drive cannot be started if any of the interlocks are open.
The function could be used for a damper interlock, preventing the drive to start with damper
closed.
M3.5.1.16
P
RESET
FREQUENCY
SELECTION
0
M3.5.1.17
P
RESET
FREQUENCY
SELECTION
1
M3.5.1.18
P
RESET
FREQUENCY
SELECTION
2
Connect a digital input to these functions with the programming method presented in chapter
3.5.2) to be able to apply Preset frequencies 1 to 7 (see Table 53 and pages 37, 40 and 68).
Output frequency
Maximum
frequency
Old deceleration
time
New deceleration time
(Old optimizing percentage)
Time
HW100 K29.fh11
Содержание SmartVFD HVAC MR4
Страница 7: ...Honeywell 5 SAFETY ...
Страница 49: ...Honeywell 47 COMMISSIONING ...
Страница 78: ...STARTUP Honeywell 6 ...