P
RODUCT
DATA
Honeywell
• 62
7
7.1.2
Mains voltage 380-480V
Table 20. Power ratings, supply voltage 380-480V.
NOTE:
The rated currents in given ambient temperatures (in Table 21) are achieved only when
the switching frequency is equal to or less than the factory default.
Mains voltage 380-480V, 50-60 Hz, 3~
Converter
type
Loadability
Motor shaft power
Low
*
*
See chapter 7.1.3
400V supply
480V supply
Rated continuous
current I
L
[A]
10% overload
current
[A]
10% overload
104°F
[kW]
10% overload
104°F
[HP]
MR4
C 0015
3.4
3.7
1.1
1.5
C 0020
4.8
5.3
1.5
2.0
C 0030
5.6
6.2
2.2
3.0
C 0050
8.0
8.8
3.0
5.0
C 0075
**
**
Given low loadabilities valid for 480V drives at a switching frequency of
4kHz
12.0
13.2
5.5
7.5
MR5
C 0100
16.0
17.6
7.5
10
C 0150
23.0
25.3
11.0
15.0
C 0200**
31.0
34.1
15.0
20.0
MR6
C 0250
38.0
41.8
18.5
25.0
C 0300
46.0
50.6
22.0
30.0
C 0400**
61.0
67.1
30.0
40.0
MR7
C 0500
72.0
79.2
37.0
50.0
C 0600
87.0
95.7
45.0
60.0
C 0750
105.0
115.5
55.0
75.0
MR8
C 1000
140.0
154.0
75
100
C 1250
170.0
187.0
90
125
C 1500
205.0
225.5
110
150
MR9
C 2000
261.0
287.1
132
200
C 2500
310.0
341.0
160
250
Содержание SmartVFD HVAC MR4
Страница 7: ...Honeywell 5 SAFETY ...
Страница 49: ...Honeywell 47 COMMISSIONING ...