Multi-pump mini-wizard
The Multi-Pump mini-wizard asks the most important questions for setting up a Multi-Pump sys-
tem. The PID mini-wizard always precedes the Multi-Pump mini-wizard. The keypad will guide
you through the questions as in chapter 1.2 then to be followed by the set of questions below:
If Autochange function is enabled the following three questions will appear. If Autochange will
not be used the Wizard jumps directly to question 21.
After this, the keypad will show the digital input and relay output configuration recommended
by the application. Write these values down for future reference.
14
Wake-up level 1
Range depends on selected pro-
cess unit.
15
Number of motors
1...4
16
Interlock function
0 = Not used
1 = Enabled
17
Autochange
0 = Disabled
1 = Enabled
18
Include FC
0 = Disabled
1 = Enabled
19
Autochange interval
0.0...3000.0 h
20
Autochange: Frequency limit
0.00...50.00 Hz
21
Bandwidth
0...100%
22
Bandwidth delay
0...3600 s