3.5.7.3
Digital outputs, slot B (Basic)
Table 29. Digital output settings on basic I/O board
Code
Parameter
Min
Max
Unit
Default
ID
Description
M3.5.3.2.1
Basic R01 function
0
35
2
11001
Function selection for Basic
R01:
0 = None
1 = Ready
2 = Run
3 = General fault
4 = General fault inverted
5 = General alarm
6 = Reversed
7 = At speed
8 = Motor regulator active
9 = Preset speed active
10 = Keypad control active
11 = I/O B control activated
12 = Limit supervision 1
13 = Limit supervision 2
14 = Start signal active
15 = Reserved
16 = Fire Mode activation
17 = RTC time chnl 1 control
18 = RTC time chnl 2 control
19 = RTC time chnl 3 control
20 = FB ControlWord B13
21 = FB ControlWord B14
22 = FB ControlWord B15
23 = PID1 in Sleep mode
24 = Reserved
25 = PID1 supervision limits
26 = PID2 supervision limits
27 = Motor 1 control
28 = Motor 2 control
29 = Motor 3 control
30 = Motor 4 control
31 = Reserved (Always
open)
32 = Reserved (Always
open)
33 = Reserved (Always
open)
34 = Maintenance alarm
35 = Maintenance fault
M3.5.3.2.2
Basic R01 ON delay
0.00
320.00
s
0.00
11002 ON delay for relay
M3.5.3.2.3 Basic R01 OFF delay
0.00
320.00
s
0.00
11003 OFF delay for relay
M3.5.3.2.4
Basic R02 function
0
35
3
11004 See M3.5.3.2.1
M3.5.3.2.5
Basic R02 ON delay
0.00
320.00
s
0.00
11005 See M3.5.3.2.2.
M3.5.3.2.6 Basic R02 OFF delay
0.00
320.00
s
0.00
11006 See M3.5.3.2.3.
M3.5.3.2.7
Basic R03 function
0
35
1
11007
See M3.5.3.2.1.
Not visible if only 2 output
relays are installed