P
OWER
CABLING
Honeywell
• 30
4
Figure 25. Additional protective grounding connector
Figure 26. Re-mounting of cover components
8
Check the connection of the grounding cable to the motor and the drive terminals
marked with
.
NOTE
: Two protective conductors are required according to standard EN61800-
5-1. See Figure 25 and chapter Grounding and ground fault protection. Use an
M5 size screw and tighten it to 2.0 Nm (17.7 lb-in.).
9
Re-mount the cable protection plate (Figure 26) and the cover of the drive.
= M5; 2Nm