• 67
HVAC A
PPLICATION
Figure 9. AI1 threshold
M3.2.10
K
EYPAD
M
ASTER
S
TOP
The AC drive can be forced to stop state from keypad stop button even if it is controlled from
another control place (
Remote
). If this measure is taken, the drive goes to the alarm state and
cannot be restarted from the remote control place before the start button has been pressed
(while in
Remote
).
You can still momentarily switch to
Local
and start there but when going back to
Remote
a start
button press is needed. This also applies after a power-down as the state of this function is re-
tained in memory.
The function can be enabled or disabled with this parameter.
M3.3.10
P
RESET
FREQUENCY
MODE
You can use the preset frequency parameters to define certain frequency references in ad-
vance. These references are then applied by activating/inactivating digital inputs connected to
parameters M3.5.1.16, M3.5.1.17 and M3.5.1.18 ((
Preset frequency selection 0, Preset fre-
quency selection 1
and
Preset frequency selection 2
). Two different logics can be selected:
M3.3.11
TO
M3.3.18
P
RESET
FREQUENCIES
1
TO
7
The values of the preset frequencies are automatically limited between the minimum and max-
imum frequencies (M3.3.1 and M3.3.2). See table below.
Selection
number
Selection name
Note
0
Binary coded
Combine activated inputs according to Table 53 to choose the
Preset frequency needed.
1
Number (of inputs used) According to how many of the inputs assigned for
Preset fre-
quency selections
are active you can apply the
Preset fre-
quencies
1 to 3.
Start
command
1 = Active
0 = Not active
AI1 threshold -2%
AI1 threshold
0%
100%
AI1
HW100K31.fh11