Group 3.12: PID-controller 1
3.5.14.1
Basic settings
Table 39.
Code
Parameter
Min
Max
Unit
Default
ID
Description
M3.12.1.1
PID gain
0.00
1000.00
%
100.00
118
If the value of the parameter
is set to 100% a change of
10% in the error value
causes the controller output
to change by 10%.
M3.12.1.2
PID integration time
0.00
600.00
s
1.00
119
If this parameter is set to
1,00 second a change of
10% in the error value
causes the controller output
to change by 10.00%/s.
M3.12.1.3
PID derivation time
0.00
100.00
s
0.00
132
If this parameter is set to
1,00 second a change of
10% in the error value during
1.00 s causes the controller
output to change by 10.00%.
M3.12.1.4 Process unit selection
1
40
1
1036 Select unit for actual value.
M3.12.1.5
Process unit min
Varies
Varies
Varies
0
1033
M3.12.1.6
Process unit max
Varies
Varies
Varies
100
1034
M3.12.1.7 Process unit decimals
0
4
2
1035
Number of decimals for pro-
cess unit value
M3.12.1.8
Error inversion
0
1
0
340
0 = Normal (Feedback < Set-
point -> Increase PID output)
1 = Inverted (Feedback <
Setpoint ->
Decrease PID out-
put
)
M3.12.1.9 Dead band hysteresis
Varies
Varies
Varies
0
1056
Dead band area around the
setpoint in process units.The
PID output is locked if the
feedback stays within the
deadband area for a pre-
defined time.
M3.12.1.10
Dead band delay
0.00
320.00
s
0.00
1057
If the feedback stays within
the dead band area for a pre-
defined time, the output is
locked.