P
OWER
CABLING
Honeywell
• 22
4
4.1.1.1
Cable and fuse sizes, frames MR4 to MR6, North America
The recommended fuse types are gG/gL (IEC 60269-1) or class T (UL & CSA). The fuse volt-
age rating should be selected according to the supply network. The final selection should be
made according to local regulations, cable installation conditions and cable specification. Big-
ger fuses than what is recommended below shall not be used.
Check that the fuse operating time is less than 0.4 seconds. Operating time depends on used
fuse type and impedance of the supply circuit. Consult the factory about faster fuses. Honey-
well offers recommendations also for high speed J (UL & CSA ), aR (UL recognized, IEC
60269-4) and gS (IEC 60269-4) fuse ranges.
Table 8. Cable and fuse sizes for Honeywell Smart VFD HVAC (MR4 to MR6)
The cable dimensioning is based on the criteria of the Underwriters’ Laboratories UL508C:Cables must
be PVC-isolated; Max ambient tempe86°F, max temperature of cable s158°F; Use only
cables with concentric copper shield; Max number of parallel cables is 9.
When using cables in parallel,
NOTE HOWEVER
that the requirements of both the cross-sectional
area and the max number of cables must be observed.
For important information on the requirements of the grounding conductor, see standard Underwriters’
Laboratories UL508C.
For the correction factors for each temperature, see the instructions of standard Underwriters’ Labora-
tories UL508C.
Frame
Type
*
*. For more information on type code, see page 8.
I
L
[A]
Fuse
(class T)
[A]
Mains, motor and
ground cable
Cu
Terminal cable size
Main terminal
Ground
terminal
MR4
C 0015
3.4
6
AWG14
AWG24-AWG10 AWG17-AWG10
C 0020
4.8
6
AWG14
AWG24-AWG10 AWG17-AWG10
C 0030
5.6
10
AWG14
AWG24-AWG10 AWG17-AWG10
C 0050
8.0
10
AWG14
AWG24-AWG10 AWG17-AWG10
C 0075
12.0
20
AWG14
AWG24-AWG10 AWG17-AWG10
MR5
C 0100
16.0
25
AWG10
AWG20-AWG5
AWG17-AWG8
C 0150
23.0
30
AWG10
AWG20-AWG5
AWG17-AWG8
C 0200
31.0
40
AWG8
AWG20-AWG5
AWG17-AWG8
MR6
C 0250
38.0
50
AWG4
AWG13-AWG0
AWG13-AWG2
C 0300
46.0
60
AWG4
AWG13-AWG0
AWG13-AWG2
C 0400
**
**. The 460V models require 90-degree wire to meet UL regulations
61.0
80
AWG4
AWG13-AWG0
AWG13-AWG2