HVAC A
PPLICATION
Honeywell
• 64
3.5.18
Group 3.16: Fire mode
Drive ignores all commands from keypad, fieldbuses and PC tool and runs at preset frequency
when activated. If activated, alarm sign is shown on the keypad and
warranty is void
. In order
to enable the function, you need to set a password in the description field for parameter
Fire
Mode password
.
NOTE! THE WARRANTY IS VOID IF THIS FUNCTION IS ACTIVATED!
There is also a differ-
ent password for test mode to be used for testing the Fire Mode without the warranty becoming
void.
Table 52. Fire mode parameters
Code
Parameter
Min
Max
Unit
Default
ID
Description
M3.16.1 Fire Mode password
0
9999
0
1599
1001 = Enabled
1234 = Test mode
M3.16.2 Fire Mode activation
DigIN Slot0.2 1596
FALSE = Fire Mode active
TRUE = No action
M3.16.3 Fire Mode frequency
0
M3.3.2
Hz
0.00
1598
Frequency used when Fire
Mode is activated.
M3.16.4
Fire Mode status
0
3
0
1597
Monitoring value (see also
Table 14)
0=Disabled
1=Enabled
2=Activated (E DI
Open)
3=Test Mode