HVAC A
PPLICATION
Honeywell
• 60
3.5.15
Group 3.13: PID-controller 2
3.5.15.1
Basic settings
For more detailed information, see chapter 3.5.14.
Table 46.
3.5.15.2
Setpoints
Table 47.
Code
Parameter
Min
Max
Unit
Default
ID
Description
M3.13.1.1
Enable PID
0
1
0
1630
0 = Disabled
1 = Enabled
M3.13.1.2
Output in Stop
0.0
100.0
%
0.0
1100
The output value of the PID
controller in % of its maxi-
mum output value while it is
stopped from digital input
M3.13.1.3
PID gain
0.00
1000.00
%
100.00
1631
M3.13.1.4
PID integration time
0.00
600.00
s
1.00
1632
M3.13.1.5
PID derivation time
0.00
100.00
s
0.00
1633
M3.13.1.6
Process unit selection
0
40
1
1635
M3.13.1.7
Process unit min
Varies
Varies
Varies
0
1664
M3.13.1.8
Process unit max
Varies
Varies
Varies
100
1665
M3.13.1.9
Process unit decimals
0
4
2
1666
M3.13.1.10
Error inversion
0
1
0
1636
M3.13.1.11 Dead band hysteresis
Varies
Varies
Varies
0.0
1637
M3.13.1.12
Dead band delay
0.00
320.00
s
0.00
1638
Code
Parameter
Min
Max
Unit
Default
ID
Description
M3.13.2.1
Keypad setpoint 1
0.00
100.00
Varies
0.00
1640
M3.13.2.2
Keypad setpoint 2
0.00
100.00
Varies
0.00
1641
M3.13.2.3
Setpoint ramp time
0.00
300.00
s
0.00
1642
M3.13.2.4
Setpoint source 1
selection
0
16
1
1643
M3.13.2.5
Setpoint 1 minimum
-200.00
200.00
%
0.00
1644
Minimum value at analog
signal minimum.
M3.13.2.6
Setpoint 1 maximum
-200.00
200.00
%
100.00
1645
Maximum value at analog
signal maximum.
M3.13.2.7
Setpoint source 2
selection
0
16
0
1646 See M3.13.2.4.
M3.13.2.8
Setpoint 2 minimum
-200.00
200.00
%
0.00
1647
Minimum value at analog
signal minimum.
M3.13.2.9
Setpoint 2 maximum
-200.00
200.00
%
100.00
1648
Maximum value at analog
signal maximum.