HVAC A
PPLICATION
3.4.3
Timer functions monitoring
Here you can monitor values of timer functions and the Real Time Clock.
Table 15. Monitoring of timer functions
3.4.4
PID1 controller monitoring
Table 16. PID1-controller value monitoring
3.4.5
PID2 controller monitoring
Table 17. PID2-controller value monitoring
Monitoring value
Unit
ID
Description
M2.3.1
TC 1, TC 2, TC 3
1441
Possible to monitor the statuses of the
three Time Channels (TC)
M2.3.2
Interval 1
1442
Status of timer interval
M2.3.3
Interval 2
1443
Status of timer interval
M2.3.4
Interval 3
1444
Status of timer interval
M2.3.5
Interval 4
1445
Status of timer interval
M2.3.6
Interval 5
1446
Status of timer interval
M2.3.7
Timer 1
s
1447
Remaining time on timer if active
M2.3.8
Timer 2
s
1448
Remaining time on timer if active
M2.3.9
Timer 3
s
1449
Remaining time on timer if active
M2.3.10
Real time clock
1450
Monitoring value
Unit
ID
Description
M2.4.1
PID1 setpoint
Varies
20
Process units selected with parameter
M2.4.2
PID1 feedback
Varies
21
Process units selected with parameter
M2.4.3
PID1 error value
Varies
22
Process units selected with parameter
M2.4.4
PID1 output
%
23
Output to motor control or external control
(AO)
M2.4.5
PID1 status
24
0=Stopped
1=Running
3=Sleep mode
4=In dead band (see page 54)
Monitoring value
Unit
ID
Description
M2.5.1
PID2 setpoint
Varies
83
Process units selected with parameter
M2.5.2
PID2 feedback
Varies
84
Process units selected with parameter
M2.5.3
PID2 error value
Varies
85
Process units selected with parameter
M2.5.4
PID2 output
%
86
Output to external control (AO)
M2.5.5
PID2 status
87
0=Stopped
1=Running
2=In dead band (see page 54)