18-15
Chapter 18
Tips/FAQ/Troubleshooting
E014 Ground fault error
This is a function to protect the inverter by the
detection of ground faults between the inverter output
and the motor at power-on.
The function doesn’t work when there is a voltage
induced in the motor due to idling or when the inverter
trips.
When the control circuit power (R0, T0, or 24V power
supply) has been turned ON prior to the main circuit
power R, S, or T, the function is activated at the time
the main circuit power is turned ON.
E015 Incoming overvoltage
error
This error occurs if high incoming voltage level is held
for 100 seconds continuously while the inverter output
is stopped when incoming overvoltage level [bb-61] is
set to 01. It occurs when the P-N voltage exceeds the
voltage level set in the incoming overvoltage level
selection [bb-62] due to incoming voltage.
Setting the ground fault detection selection [bb-64] to
00 disables the ground fault function. Setting it to 01
enables the function.
Error occurred after
power was turned
ON.
• Incoming voltage is high. • Re-examination of the power supply environment is required.
• Power supply has
become unstable.
• The power supply environment may have been changed due to
facility replacement or the like.
Re-examination of the power supply environment is required.
Error occurred after
long hours of use.
Occurrence
Estimated cause(s)
Exemplar measures to be taken
Error occurred as
the power supply
was turned ON.
• Ground faults of wires
or the motor
• Motor insulation
deterioration
• Turn OFF the power, remove the wires connected to the motor, and
then check the motor and the wires.
A ground fault may have been
occurred.
• Turning ON the power supply in a ground fault state results in a
failure. Do not turn ON the power when you check the motor and
motor wires.
E014
Occurrence
Estimated cause(s)
Exemplar measures to be taken
E015
Содержание SJ Series
Страница 39: ...5 4 Chapter 5 Included Items Memo ...
Страница 52: ...6 13 Chapter 6 Installation Model P1 P1 200V class P1 02950 L P1 550L Dimension W mm H mm D mm 480 700 250 ...
Страница 55: ...6 16 Chapter 6 Installation Memo ...
Страница 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Страница 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Страница 145: ...10 10 Chapter 10 Test Run Memo ...
Страница 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Страница 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Страница 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Страница 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Страница 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Страница 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Страница 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Страница 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Страница 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Страница 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Страница 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Страница 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Страница 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Страница 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Страница 661: ...20 11 Chapter 20 Specifications Model P1 P1 200V class 02950 L 550L Dimension W mm H mm D mm 700 480 250 ...
Страница 662: ...20 12 Chapter 20 Specifications Model P1 P1 400V class 01760 H 750H 02130 H 900H Dimension W mm H mm D mm 390 700 270 ...
Страница 663: ...20 13 Chapter 20 Specifications Model P1 P1 400V class 02520 H 1100H 03160 H 1320H Dimension W mm H mm D mm 480 740 270 ...
Страница 678: ...21 7 Chapter 21 Technical Notes SJ700D SJ P1 ND normal duty SJ700D 550LFF3 P1 02950 LFEF P1 550LFF ...
Страница 686: ...21 15 Chapter 21 Technical Notes SJ700B SJ P1 LD low duty VLD very low duty SJ700B 750LFF P1 02950 LFEF P1 550LFF ...
Страница 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...