14-23
Chapter 14
RS485 Communication
Command settings for assigning master inverters
Set-up destinations
M: Perform the setting to inverters having station
numbers designated in [CF-20] and [CF-21] (=
master inverters).
14.5.3
EzCOM Operation
(1) A master inverter transmits data to slave
inverters according to the settings made to the
master inverter.
(2) The controlling inverter transmits a master
switching command, and then a master inverter
is switched.
(3) The next master inverter transmits data to slave
inverters as described in (1).
(4) Processes of (2) and (3) will follow, and the
whole processes will be repeated likewise.
*3) As for the transmission destination register and
the transmission source register, specify the
register address obtained by subtracting one
from the register No. For information on register
address, please contact the sales officer of our
company shown on the back cover.
• Entire communication data is transmitted to all
stations because EzCOM communication is
performed by broadcast communication. As a
result, a slave not designated as transmission
destinations on the master side receives data once,
but internally discards the data which is not
addressed to it.
Item
Parameter
Data
Set-up
Destination
Description
Number of EzCOM transmitting
data
[CF-23]
01~05
M
Sets how many of the registers 1 to 5 shown
below need to be transferred in EzCOM
communication.
EzCOM transmission destination
station number 1
[CF-24]
1~247
M
Station number for transmission destination 1.
EzCOM transmission destination
register *3)
[CF-25]
0000h~FFFFh
M
Sets the high-order register of transmission
destination 1.
EzCOM transmission source 1
register *3)
[CF-26]
0000h~FFFFh
M
Sets the low-order register of transmission
destination 1.
EzCOM transmission destination
station number 2
[CF-27]
1~247
M
Station number for transmission destination 2.
EzCOM transmission destination 2
register *3)
[CF-28]
0000h~FFFFh
M
Sets the high-order register of transmission
destination 2.
EzCOM transmission source 2
register *3)
[CF-29]
0000h~FFFFh
M
Sets the low-order register of transmission
destination 2.
EzCOM transmission destination
station number 3
[CF-30]
1~247
M
Station number for transmission destination 3.
EzCOM transmission destination 3
register *3)
[CF-31]
0000h~FFFFh
M
Sets the high-order register of transmission
destination 3.
EzCOM transmission source 3
register *3)
[CF-32]
0000h~FFFFh
M
Sets the low-order register of transmission
destination 3.
EzCOM transmission destination
station number 4
[CF-33]
1~247
M
Station number for transmission destination 4.
EzCOM transmission destination 4
register *3)
[CF-34]
0000h~FFFFh
M
Sets the high-order register of transmission
destination 4.
EzCOM transmission source 4
register *3)
[CF-35]
0000h~FFFFh
M
Sets the low-order register of transmission
destination 4.
EzCOM transmission destination
station number 5
[CF-36]
1~247
M
Station number for transmission destination 5.
EzCOM transmission destination 5
register *3)
[CF-37]
0000h~FFFFh
M
Sets the high-order register of transmission
destination 5.
EzCOM transmission source 5
register *3)
[CF-38]
0000h~FFFFh
M
Sets the low-order register of transmission
destination 5.
▼
!
Содержание SJ Series
Страница 39: ...5 4 Chapter 5 Included Items Memo ...
Страница 52: ...6 13 Chapter 6 Installation Model P1 P1 200V class P1 02950 L P1 550L Dimension W mm H mm D mm 480 700 250 ...
Страница 55: ...6 16 Chapter 6 Installation Memo ...
Страница 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Страница 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Страница 145: ...10 10 Chapter 10 Test Run Memo ...
Страница 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Страница 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Страница 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Страница 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Страница 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Страница 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Страница 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Страница 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Страница 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Страница 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Страница 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Страница 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Страница 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Страница 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Страница 661: ...20 11 Chapter 20 Specifications Model P1 P1 200V class 02950 L 550L Dimension W mm H mm D mm 700 480 250 ...
Страница 662: ...20 12 Chapter 20 Specifications Model P1 P1 400V class 01760 H 750H 02130 H 900H Dimension W mm H mm D mm 390 700 270 ...
Страница 663: ...20 13 Chapter 20 Specifications Model P1 P1 400V class 02520 H 1100H 03160 H 1320H Dimension W mm H mm D mm 480 740 270 ...
Страница 678: ...21 7 Chapter 21 Technical Notes SJ700D SJ P1 ND normal duty SJ700D 550LFF3 P1 02950 LFEF P1 550LFF ...
Страница 686: ...21 15 Chapter 21 Technical Notes SJ700B SJ P1 LD low duty VLD very low duty SJ700B 750LFF P1 02950 LFEF P1 550LFF ...
Страница 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...