12-3-8
Chapter 12
Inverter Functions
Offline auto-tuning
Check the control type [AA121].
For the induction motor (IM), make sure that the
control type [AA121] is set to the one for IM. For
the synchronous motor (SM) or permanent
magnetic motor (PMM), make sure that the
control type [AA121] is set to the one for PMM.
Set the auto-tuning selection [HA-01].
In the auto-tuning selection [HA-01], 01:
Non-revolving or 02: Revolving is set. The tuning
does not begin at this stage. Only “non-revolving”
can be chosen for synchronous motor (SM) /
permanent magnetic motor (PMM).
Set a start command for tuning.
Pressing OPERATION button on the operator
keypad starts the tuning, Pressing STOP button
terminates the tuning, However tuning data are
not saved.
The inverter automatically operates.
Output of a preset pattern is given to the motor. If
the auto-tuning selection [HA-01] is set to 01:
Non-revolving, non-revolving output of three
different patterns is given.
If the auto-tuning selection [HA-01] is set to 02:
Revolving, acceleration and deceleration are
repeated twice in addition to the above output.
The frequency increases up to 80% of the base
frequency.
After the above operation finishes, the output
with no revolution is checked as final check.
The tuning finished.
When the tuning End display appears, the tuning
finishes. Use STOP key to cancel the End
display.
Online auto-tuning
Perform the offline auto-tuning.
The online auto-tuning works with the
designated motor constants and the offline
auto-tuning described on the left is performed.
The online tuning selection [HA-03] is set.
Set the online tuning selection [HA-03] to 01:
Enabled.
Check the online auto-tuning.
The online tuning operates for up to 5 s when
every operation stops. Use the online tuning after
making sure that the operation and stop can be
made correctly by your operation command.
• In case of termination due to trip or erroneous
tuning, correct data cannot be acquired. See the
next section.
• The result of the online tuning is automatically
reflected in up to 5 s after the stop. It is not
reflected if the operation is restarted during the
tuning.
• The online tuning is not performed if the servo-on
function [SON] or forcing function [FOC] is
working.
• In the factory setting, the offline auto-tuning can be
started by the operation key on the operator
keypad. It can be changed to a designated
operation command by changing the operation
command [HA-02] of the auto-tuning.
▼
1
2
3
4
5
▼
1
2
3
!
Содержание SJ Series
Страница 39: ...5 4 Chapter 5 Included Items Memo ...
Страница 52: ...6 13 Chapter 6 Installation Model P1 P1 200V class P1 02950 L P1 550L Dimension W mm H mm D mm 480 700 250 ...
Страница 55: ...6 16 Chapter 6 Installation Memo ...
Страница 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Страница 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Страница 145: ...10 10 Chapter 10 Test Run Memo ...
Страница 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Страница 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Страница 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Страница 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Страница 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Страница 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Страница 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Страница 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Страница 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Страница 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Страница 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Страница 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Страница 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Страница 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Страница 661: ...20 11 Chapter 20 Specifications Model P1 P1 200V class 02950 L 550L Dimension W mm H mm D mm 700 480 250 ...
Страница 662: ...20 12 Chapter 20 Specifications Model P1 P1 400V class 01760 H 750H 02130 H 900H Dimension W mm H mm D mm 390 700 270 ...
Страница 663: ...20 13 Chapter 20 Specifications Model P1 P1 400V class 02520 H 1100H 03160 H 1320H Dimension W mm H mm D mm 480 740 270 ...
Страница 678: ...21 7 Chapter 21 Technical Notes SJ700D SJ P1 ND normal duty SJ700D 550LFF3 P1 02950 LFEF P1 550LFF ...
Страница 686: ...21 15 Chapter 21 Technical Notes SJ700B SJ P1 LD low duty VLD very low duty SJ700B 750LFF P1 02950 LFEF P1 550LFF ...
Страница 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...