12-17-12
Chapter 12
Inverter Functions
Example of the Control on the Secondary Side
(AF120 = 02: Enabled (secondary side)
• When Enabled (secondary side) is selected, using in
combination with the brake control 2 is available.
Once the operation command is received, the
inverter turns on
the control signal 039[CON].
The operation varies depending on whether the
contactor check signal 112[COK] is set to the
input terminal function.
With
[COK]
setting
The inverter turns on the control signal
039[CON] and, if the 112[COK] is not turned on
during the contactor check time, the inverter
trips with the [Er110] contactor error.
Without
[COK]
setting
After the control signal 039[CON] is turned on,
there is a waiting time for the start waiting time
to pass.
The inverter starts the output and is in the servo
lock status at the present location
for the servo lock time at start.
After the brake release delay time passes, the
brake release signal 037[BRK] is turned on.
The operation varies depending on whether the
brake check signal 037[BOK] is set to the input
terminal function.
With
[BOK]
setting
If the 037[BOK] is not turned on during the
brake check waiting time, the inverter trips with
the [E036] brake error outputting the fault
signal 038[BER].
Without
[BOK]
setting
After the release signal 037[BRK] signal is
turned on, there is a waiting for the servo lock
time at start to pass.
After the servo lock time at start passes, there is
an acceleration.
Once the operation command is turned off, the
inverter decelerates and is in the position servo
lock status for the servo lock time at stop.
After the brake release delay time passes, the
brake release signal 037[BRK] is turned off.
The operation varies depending on whether the
brake check signal 037[BOK] is set to the input
terminal function.
With
[BOK]
setting
The inverter turns off the release signal
037[BOK], and if the 037[BOK] is not turned off
during the brake check time, the inverter trips
with the [E036] brake error outputting the fault
signal 038[BER].
Without
[BOK]
setting
After the release signal [BRK] signal is turned
off, there is a waiting for the servo lock time at
stop to pass.
The inverter shuts off the output and, after the
contactor release delay time passes, the
control signal 039[CON] is turned off.
The operation varies depending on whether
the contactor check signal 112[COK] is set to
the input terminal function.
With
[COK]
setting
If the 112[COK] is not turned off during the
contactor check time, the inverter trips with the
[E110] contactor error.
Without
[COK]
setting
The inverter still does nothing.
(1)
(2)
(3)
(4)
(5)
(7)
(9)
(10)
(11)
Operation
command
Output
frequency
Contactor control signal
039[CON]
Contactor check time
Contactor check signal
112[COK]
Brake release delay time
(2)
(3)
(8)
(9)
(1)
Brake release signal
037[BRK]
Brake check signal
037[BOK]
Brake check waiting time
Brake check waiting time
(4)
Start
waiting
time
Servo lock
time at start
Brake release delay time
Contactor check time
(10)
(5)
(11)
Servo lock
time at stop
(7)
Contactor release delay time
(6)
(6)
(8)
▼
Содержание SJ Series
Страница 39: ...5 4 Chapter 5 Included Items Memo ...
Страница 52: ...6 13 Chapter 6 Installation Model P1 P1 200V class P1 02950 L P1 550L Dimension W mm H mm D mm 480 700 250 ...
Страница 55: ...6 16 Chapter 6 Installation Memo ...
Страница 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Страница 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Страница 145: ...10 10 Chapter 10 Test Run Memo ...
Страница 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Страница 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Страница 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Страница 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Страница 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Страница 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Страница 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Страница 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Страница 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Страница 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Страница 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Страница 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Страница 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Страница 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Страница 661: ...20 11 Chapter 20 Specifications Model P1 P1 200V class 02950 L 550L Dimension W mm H mm D mm 700 480 250 ...
Страница 662: ...20 12 Chapter 20 Specifications Model P1 P1 400V class 01760 H 750H 02130 H 900H Dimension W mm H mm D mm 390 700 270 ...
Страница 663: ...20 13 Chapter 20 Specifications Model P1 P1 400V class 02520 H 1100H 03160 H 1320H Dimension W mm H mm D mm 480 740 270 ...
Страница 678: ...21 7 Chapter 21 Technical Notes SJ700D SJ P1 ND normal duty SJ700D 550LFF3 P1 02950 LFEF P1 550LFF ...
Страница 686: ...21 15 Chapter 21 Technical Notes SJ700B SJ P1 LD low duty VLD very low duty SJ700B 750LFF P1 02950 LFEF P1 550LFF ...
Страница 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...