12-3-1
Chapter 12
Inverter Functions
12.3 Basic setting of motor
12.3.1
Parameter setting of motor
rating data
• Want to make setting suitable for the motor.
• Unstable motor operation
About induction motor (IM)
About synchronous motor (SM) / permanent
magnetic motor (PMM)
• Basic parameters to control and protect the motor
are set.
• The following basic parameters need to be set for
any control type.
• The motor operation could be stabilized if the motor
items are set to the inverter.
• The induction motor (IM) and synchronous motor
(SM) / permanent magnet motor (PMM) are set
separately.
Items of
Induction motor
Parameters of inverter
Setting range (unit)
Description
Capacity
[Hb102]
Selection of
motor capacity
0.01
~
160.00 (kW)
Sets the motor capacity.
Number of
motor poles
[Hb103]
Selection of
number of
motor
poles
2-48 (poles)
Sets the number of
motor poles.
Frequency
[Hb104]
Base frequency
10.00~590.00 (Hz)
Sets the base frequency of motor.
[Hb105]
Max. frequency
10.00~590.00 (Hz)
Sets the max. frequency of motor.
Voltage
[Hb106]
Rated voltage of
motor
1~1000 (V)
Sets the rated voltage of motor.
Current
[Hb108]
Rated current of
motor
0.01~10000.00 (A)
Sets the rated current of motor.
Items of
PM
motor
Parameters of inverter
Setting range (unit)
Description
Capacity
[Hd102]
Selection of
motor capacity
0.01~160.00 (kW)
Sets the motor capacity.
Number of
poles
[Hd103]
Selection of
number of poles
2-48 (poles)
Sets the number of poles.
Frequency
[Hd104]
Base frequency
10.00~590.00 (Hz)
Sets the base frequency of motor.
[Hd105]
Max. frequency
10.00~590.00 (Hz)
Sets the max. frequency of motor.
Voltage
[Hd106]
Rated voltage of
motor
1~1000 (V)
Sets the rated voltage of motor.
Current
[Hd108]
Rated current of
motor
0.01~10000.00 (A)
Sets the rated current of motor.
Q
A
Содержание SJ Series
Страница 39: ...5 4 Chapter 5 Included Items Memo ...
Страница 52: ...6 13 Chapter 6 Installation Model P1 P1 200V class P1 02950 L P1 550L Dimension W mm H mm D mm 480 700 250 ...
Страница 55: ...6 16 Chapter 6 Installation Memo ...
Страница 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Страница 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Страница 145: ...10 10 Chapter 10 Test Run Memo ...
Страница 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Страница 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Страница 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Страница 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Страница 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Страница 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Страница 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Страница 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Страница 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Страница 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Страница 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Страница 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Страница 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Страница 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Страница 661: ...20 11 Chapter 20 Specifications Model P1 P1 200V class 02950 L 550L Dimension W mm H mm D mm 700 480 250 ...
Страница 662: ...20 12 Chapter 20 Specifications Model P1 P1 400V class 01760 H 750H 02130 H 900H Dimension W mm H mm D mm 390 700 270 ...
Страница 663: ...20 13 Chapter 20 Specifications Model P1 P1 400V class 02520 H 1100H 03160 H 1320H Dimension W mm H mm D mm 480 740 270 ...
Страница 678: ...21 7 Chapter 21 Technical Notes SJ700D SJ P1 ND normal duty SJ700D 550LFF3 P1 02950 LFEF P1 550LFF ...
Страница 686: ...21 15 Chapter 21 Technical Notes SJ700B SJ P1 LD low duty VLD very low duty SJ700B 750LFF P1 02950 LFEF P1 550LFF ...
Страница 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...