12-15-5
Chapter 12
Inverter Function
External DC braking via terminal function
• Assign 030 [DB] to input terminal functions
[CA-01] to [CA-11].
• When [AF101]=00 or 01, DC braking will be
applied depending on whether the [DB] terminal is
on or off.
• Adjust the braking force by adjusting the [AF105]
DC braking force.
• When you set the [AF104] DC braking delay time,
the inverter output will be shut off within the set
period of delay, and the motor will run freely during
the period. (Ex. 11), (Ex. 14)
• DC braking will be restarted after the set period
has elapsed.
• Select the braking mode by the DC braking/edge
or level selection [AF107], and then make any
other necessary settings suitable for your system.
• When [AF107]=00: After [DB] is turned on, the
inverter performs DC braking for the time set for
[AF106] . (Example 9) to (Example 11)
• When [AF107]=01: The inverter performs DC
braking only when [DB] is on. (Ex. 12) to (Ex. 14)
• When setting [AF105] DC braking force, [AF106]
DC braking time, or the ON time of the [DB]
terminal (input terminal function 030), pay
attention to the heat generation on the motor.
• The setting for the [DB] terminal is given priority
over operation commands. (Ex. 9), (Ex. 12)
• If the [DB] terminal is turned on when the motor
speed is high, an overcurrent error or an
overvoltage error may occur.
• When the [DB] terminal is turned on, DC braking
mode that occurs when "00" is specified for
[AF102] Braking mode selection is performed
regardless of the setting for [AF102].
Edge mode: [AF107]=00
Level mode: [AF107]=01
(Ex. 9)
FW
DB
Output frequency
(Ex. 12)
FW
DB
Output frequency
(Ex. 10)
FW
DB
Output frequency
(Ex. 13)
FW
DB
Output frequency
(Ex. 11)
FW
DB
Output frequency
(Ex. 14)
FW
DB
Output frequency
A
!
[AF106]
DC braking
ON
ON
DC braking
ON
ON
[AF106]
DC braking
ON
ON
DC braking
ON
ON
[AF104]
Free-running
[AF106]
DC braking
ON
ON
DC braking
[AF104]
Free-running
ON
ON
Содержание SJ Series
Страница 39: ...5 4 Chapter 5 Included Items Memo ...
Страница 52: ...6 13 Chapter 6 Installation Model P1 P1 200V class P1 02950 L P1 550L Dimension W mm H mm D mm 480 700 250 ...
Страница 55: ...6 16 Chapter 6 Installation Memo ...
Страница 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Страница 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Страница 145: ...10 10 Chapter 10 Test Run Memo ...
Страница 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Страница 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Страница 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Страница 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Страница 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Страница 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Страница 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Страница 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Страница 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Страница 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Страница 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Страница 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Страница 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Страница 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Страница 661: ...20 11 Chapter 20 Specifications Model P1 P1 200V class 02950 L 550L Dimension W mm H mm D mm 700 480 250 ...
Страница 662: ...20 12 Chapter 20 Specifications Model P1 P1 400V class 01760 H 750H 02130 H 900H Dimension W mm H mm D mm 390 700 270 ...
Страница 663: ...20 13 Chapter 20 Specifications Model P1 P1 400V class 02520 H 1100H 03160 H 1320H Dimension W mm H mm D mm 480 740 270 ...
Страница 678: ...21 7 Chapter 21 Technical Notes SJ700D SJ P1 ND normal duty SJ700D 550LFF3 P1 02950 LFEF P1 550LFF ...
Страница 686: ...21 15 Chapter 21 Technical Notes SJ700B SJ P1 LD low duty VLD very low duty SJ700B 750LFF P1 02950 LFEF P1 550LFF ...
Страница 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...