21-38
Chapter 21
Technical Notes
21.4.4
STO Status Retention Function
The retention function that retains the blocked status of
internal safety path even if STO input is canceled is not
implemented as a safety circuit.
Therefore, if an operation command is input after
cancellation of STO input or STO input is canceled while it
is input, the inverter starts output to the motor.
Hence, to satisfy the requirement about cancellation of
emergency stop specified in EN/IEC60204-1, you need to
take either of the following measures.
(1) At the same time as STO input, set the operation
command to the inverter to stopped status
(2) Configure the system so that STO input to SJ-P1 is
canceled when system reboot is required by the user.
By setting parameters of the main unit, you can select the
following operations. (see 4.7)
(1) Trip the inverter by STO input. In this case, the
inverter is tripped and output is stopped until power is
shut off or the error reset signal for the inverter is
input.
(2) If two STO input systems to the inverter are not input
at the same time, the inverter is shut off and enters
standby mode until STO input for the two systems is
input.
21.4.5
STO Confirmation Signal Output (EDM
Signal)
The STO confirmation signal output (EDM output) is the
output signal for monitoring the input status of STO signal
and failure detection status on the internal safety path.
EDM terminal (ED+ / ED-) and wiring example
For operation of ST1/St2 and output of STO confirmation
signal against failure detection status, see the matrix
below. EDM turns ON only when both STO inputs are
correctly input and internal failure is not detected.
Signal matrix
Signal
Status 1 Status 2
Status 3
Status 4 Status 5
ST1 *1)
STO
Operation
permitted
STO
Operation
permitted
*
ST2 *1)
STO
STO
Operation
permitted
Operation
permitted
*
Failure
detection
None
None
None
None
Detected
EDM
ON
OFF
OFF
OFF
OFF
Output to
the motor
Off
Off
Off
Output
permitted
Off
*1) The following table shows the correspondence
between the input status of ST1/ST2 described
in the table above and status of contact points.
Input status
Contact point
STO
OFF
Operation permitted
ON
Control circuit terminal area
ED-
ED+
STO
confirmation
terminal
Duty
Wiring example
Содержание SJ Series
Страница 39: ...5 4 Chapter 5 Included Items Memo ...
Страница 52: ...6 13 Chapter 6 Installation Model P1 P1 200V class P1 02950 L P1 550L Dimension W mm H mm D mm 480 700 250 ...
Страница 55: ...6 16 Chapter 6 Installation Memo ...
Страница 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Страница 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Страница 145: ...10 10 Chapter 10 Test Run Memo ...
Страница 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Страница 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Страница 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Страница 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Страница 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Страница 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Страница 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Страница 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Страница 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Страница 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Страница 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Страница 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Страница 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Страница 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Страница 661: ...20 11 Chapter 20 Specifications Model P1 P1 200V class 02950 L 550L Dimension W mm H mm D mm 700 480 250 ...
Страница 662: ...20 12 Chapter 20 Specifications Model P1 P1 400V class 01760 H 750H 02130 H 900H Dimension W mm H mm D mm 390 700 270 ...
Страница 663: ...20 13 Chapter 20 Specifications Model P1 P1 400V class 02520 H 1100H 03160 H 1320H Dimension W mm H mm D mm 480 740 270 ...
Страница 678: ...21 7 Chapter 21 Technical Notes SJ700D SJ P1 ND normal duty SJ700D 550LFF3 P1 02950 LFEF P1 550LFF ...
Страница 686: ...21 15 Chapter 21 Technical Notes SJ700B SJ P1 LD low duty VLD very low duty SJ700B 750LFF P1 02950 LFEF P1 550LFF ...
Страница 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...