12-18-1
Chapter 12
Inverter Functions
12.18 Controlling the Cooling Fan of
the Inverter
12.18.1
Selecting the Operation of the
Cooling Fan
• How to run the cooling fan of the inverter all the
time
• How to cool the inverter only while it is operating
• How to stop the sound of the inverter while it is not
operating
• How to cool the inverter only when it is generating
heat
• [bA-70] Setting the selection of the cooling fan
operation allows you to set the operation of the
cooling fan.
• For [bA-70]=00, the cooling fan runs all the time.
• For [bA-70]=01, the cooling fan runs when the
inverter becomes the output status. The fan runs
for three minutes after the operation stops.
• For [bA-70]=02, the cooling fan runs depending on
the temperature of the head sink detected by the
inverter.
Parameters
• For checking the head sink temperature, see
"13.9.1 Checking the Head Sink Temperature".
• For the replacement timing of the cooling fan, see
"13.11.1 Checking the Life Cycle Monitor".
• When the instantaneous power failure or power-off
occurs while the cooling fan is running, it is
suspended regardless of the [bA-70] cooling fan
operation, and automatically resumes after the
restoration of power.
Item
Parameter
Data
Description
Selection of the Cooling
Fan Operation
[bA-70]
00
Running all the time:
The fan runs all the time.
01
Running in operation:
The fan runs automatically when the inverter becomes the
operating status. The fan continuously runs for three minutes
after the operation stops and then automatically stops.
* The cooling fan runs when the head sink temperature of
the inverter exceeds 60°C.
If the head sink temperature is
under 50°C for more than three minutes, the cooling fan is
allowed to be stopped.
02
Running depending on the temperature:
The cooling fan runs when the head sink temperature of the
inverter exceeds 40°C. If the head sink temperature is under
40°C for more than three minutes, the cooling fan
automatically stops.
Q
A
A
!
Содержание SJ Series
Страница 39: ...5 4 Chapter 5 Included Items Memo ...
Страница 52: ...6 13 Chapter 6 Installation Model P1 P1 200V class P1 02950 L P1 550L Dimension W mm H mm D mm 480 700 250 ...
Страница 55: ...6 16 Chapter 6 Installation Memo ...
Страница 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Страница 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Страница 145: ...10 10 Chapter 10 Test Run Memo ...
Страница 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Страница 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Страница 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Страница 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Страница 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Страница 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Страница 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Страница 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Страница 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Страница 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Страница 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Страница 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Страница 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Страница 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Страница 661: ...20 11 Chapter 20 Specifications Model P1 P1 200V class 02950 L 550L Dimension W mm H mm D mm 700 480 250 ...
Страница 662: ...20 12 Chapter 20 Specifications Model P1 P1 400V class 01760 H 750H 02130 H 900H Dimension W mm H mm D mm 390 700 270 ...
Страница 663: ...20 13 Chapter 20 Specifications Model P1 P1 400V class 02520 H 1100H 03160 H 1320H Dimension W mm H mm D mm 480 740 270 ...
Страница 678: ...21 7 Chapter 21 Technical Notes SJ700D SJ P1 ND normal duty SJ700D 550LFF3 P1 02950 LFEF P1 550LFF ...
Страница 686: ...21 15 Chapter 21 Technical Notes SJ700B SJ P1 LD low duty VLD very low duty SJ700B 750LFF P1 02950 LFEF P1 550LFF ...
Страница 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...