12-17-16
Chapter 12
Inverter Functions
■
Decision for Switching to the Bypass Mode
• When the [PA-04] bypass function selection is set
to 01: Enabled, if the [PA-05] bypass function delay
time passes during the forced operation without
reaching the Em-Force mode frequency setting
[PA-02] and the inverter enters the operation ready
incomplete status (output terminal [IRDY] is OFF), it
operates in the commercial operation mode
(bypass mode).
• In the bypass mode, the following functions are
operating automatically.
(1) Soft lock status (equivalent to [UA-16] = 01) The
parameters can be no longer changed. To restore
the settings, turn off
[EMF], restore the power and
then change the parameters.
(2) Auto-reset (equivalent to [bb-10] = 00)
Auto-reset is disabled.
(3) STOP key disabled (equivalent to [AA-13] = 00)
Disable the STOP/RESET keys on the operator
keypad.
(4) Operation enabled during the optional start
([oA-13] = 01, [oA-23] = 01, [oA-33] = 01)
The operation is allowed even in the optional
start-up.
• The functions except for the above operate
according to the settings.
• Once the bypass mode is turned on, the inverter
keeps shutting off until the power is off.
• While the inverter is operating immediately after the
reset, the output terminal [IRDY] is turned off for
about a second, however, the bypass mode is not
entered for that period.
・
When frequency doesn't reach to Em-Force mode
frequency setting [PA-02] while upper limiter function
is activated, accumulation of delay time is added,
A
!
!
Input terminal
[EMF]
Output terminal
[IRDY]
Output
frequency
Bypass delay time
integrated value
[IRDY] OFF
[PA-05]
[PA-02]
Output terminal
[EMFC]
Output terminal
[EMBP]
Forced operation
Bypass mode
Status
Bypass mode
delay time
Output reached
Содержание SJ Series
Страница 39: ...5 4 Chapter 5 Included Items Memo ...
Страница 52: ...6 13 Chapter 6 Installation Model P1 P1 200V class P1 02950 L P1 550L Dimension W mm H mm D mm 480 700 250 ...
Страница 55: ...6 16 Chapter 6 Installation Memo ...
Страница 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Страница 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Страница 145: ...10 10 Chapter 10 Test Run Memo ...
Страница 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Страница 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Страница 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Страница 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Страница 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Страница 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Страница 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Страница 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Страница 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Страница 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Страница 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Страница 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Страница 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Страница 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Страница 661: ...20 11 Chapter 20 Specifications Model P1 P1 200V class 02950 L 550L Dimension W mm H mm D mm 700 480 250 ...
Страница 662: ...20 12 Chapter 20 Specifications Model P1 P1 400V class 01760 H 750H 02130 H 900H Dimension W mm H mm D mm 390 700 270 ...
Страница 663: ...20 13 Chapter 20 Specifications Model P1 P1 400V class 02520 H 1100H 03160 H 1320H Dimension W mm H mm D mm 480 740 270 ...
Страница 678: ...21 7 Chapter 21 Technical Notes SJ700D SJ P1 ND normal duty SJ700D 550LFF3 P1 02950 LFEF P1 550LFF ...
Страница 686: ...21 15 Chapter 21 Technical Notes SJ700B SJ P1 LD low duty VLD very low duty SJ700B 750LFF P1 02950 LFEF P1 550LFF ...
Страница 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...