Installation
Coupling of column and chambers
GE Information
L31- 7137EN/02
12/18
11- 2016
Final coupling,
continued
Fitting the seal
The table below shows the steps for fitting the seal:
Step
Action
Illustration
1
Clean the contact surfaces
”
A
” and ”
B
” with ISOPRO-
PANOL.
Only coat surface
”B”
with
MOLYKOTE M111 lubricant.
A
B
2
Fit a new seal (20) and place
it on surface ”
A
”, referring to
”
Preparing
and
fitting
static seals
”.
See
module
’General
assembly procedures’.
20
A
3
Temporarily fit a rigid cable
(36) to counter the effects of
the seal (20) coming apart
during the coupling process
20
36
Continued on next page.
Содержание SF6
Страница 2: ...Content Instruction Manual GE Information 04 2017 D1736EN 03 2 10 This page is intentionally blank...
Страница 50: ...Installation Tightening torques GE Information 07 2016 L31 001EN 03 4 4 This page is intentionally blank...
Страница 128: ...Installation Vacuum operation GE Information 08 2016 L31 881EN04 6 6 This page is intentionally blank...
Страница 176: ...Maintenance Maintenance plan GE Information 08 2016 L51 004EN 07 8 8 This page is intentionally blank...
Страница 178: ...Maintenance Electrical wear limits GE Information 08 2016 L51 052EN 05 2 2 This page is intentionally blank...
Страница 204: ...Annexes Tooling and accessories GE Information 08 2016 L60 028EN 04 8 8 This page is intentionally blank...
Страница 206: ...Grid Solutions This page is intentionally blank...
Страница 212: ...Grid Solutions This page is intentionally blank...
Страница 216: ...Grid Solutions This page is intentionally blank...
Страница 220: ...Grid Solutions This page is intentionally blank...
Страница 258: ...Installation Lifting and positioning the pole GE Information 08 2016 L31 200EN 07 4 4 This page is intentionally blank...
Страница 286: ...Installation Coupling of column and chambers GE Information L31 7138EN 02 16 16 11 2016 This page is intentionally blank...
Страница 299: ...GE Information This page is intentionally blank...
Страница 300: ......