65
Set Transducer Block Parameters
Setup
3. Set the Tight-shut and Full-open Actions values.
The tight-shut action is an action to decrease the output pressure to a level much lower
than the 0% pressure level, or to increase it much higher than the 0% pressure level for
an air-to-close valve, when FINAL_VALUE.value is less than
FINAL_VALUE_CUTOFF_LO in order to ensure that the valve is tightly shut off.
Conversely, the full-open action is an action to increase the output pressure to a level
much higher than the 100% pressure level, or decrease it much lower than the 100%
pressure level for an air-to-close valve, when FINAL_VALUE.value is larger than
FINAL_VALUE_CUTOFF_HI in order to ensure that the valve is fully open.
A hysteresis of 1% is applied to the thresholds, FINAL_VALUE_CUTOFF_LO and
FINAL_VALUE_CUTOFF_HI.
4. Set the Thresholds for Limit Switches by:
a. Writing the threshold for the upper limit switch to LIMSW_HI_LIM, and the
threshold for the lower limit switch to LIMSW_LO_LIM.
b. Make a DI block read the on/off statuses of a limit switch by setting CHANNEL
to:
❑
2
, for reading the on/off status of the upper limit switch.
❑
3
, for reading the on/off status of the lower limit switch.
Just like hardware limit switches for a valve, on/off status signals can be generated
when the valve position read-back signal FINAL_POSITION_VALUE.value reaches
specified levels. These on/off statuses can be transferred to a DI function block.
A hysteresis of 1% is applied to the thresholds, LIMSW_HI_LIM and LIMSW_LO_LIM.
5. Write the Thresholds for Operation Result Integration Alarms by:
The FVP110 has a function to integrate the following operation result quantities
individually:
❑
TOTAL_CYCLE_COUNT (incremented by 1 at each change in the direction of
the action)
❑
TOTAL_TRAVEL (in % where full stroke = 100%)
❑
TOTAL_OPEN_TIME (in hours)
❑
TOTAL_CLOSE_TIME (in hours)
❑
TOTAL_NEAR_CLOSE_TIM (total at nearly closed time in hours)
❑
SERVO_WARN_COUNT (Total number of times of Servo output drift warning)
a. Setting values for the six items above.
b. Setting limit values for the five items below.
When these values exceed the respective thresholds below, corresponding alarms are
output. Set the thresholds as necessary.
Содержание FVP110
Страница 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Страница 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Страница 98: ...FVP 110 Fieldbus Valve Positioner Manual 82 GE Energy Figure 47 Double Acting Actuator Dimensions ...
Страница 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Страница 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 114: ...FVP 110 Fieldbus Valve Positioner Manual 98 GE Energy Table 17 View Object for Transducer Block ...
Страница 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Страница 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Страница 118: ...FVP 110 Fieldbus Valve Positioner Manual 102 GE Energy Table 19 View Object for DI1 DI2 Function Block ...
Страница 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Страница 120: ...FVP 110 Fieldbus Valve Positioner Manual 104 GE Energy Table 21 View Object for PID Function Block ...
Страница 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Страница 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Страница 239: ...223 LM Parameter List Link Master Functions ...
Страница 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Страница 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Страница 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Страница 268: ...FVP 110 Fieldbus Valve Positioner Manual 252 GE Energy Figure 84 Checking Position at Which Clamp Should Be Fixed ...
Страница 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 289: ...273 H Customer Maintenance Parts List ...
Страница 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Страница 291: ......