229
FAQs
Link Master Functions
FAQs
Q1. When the LAS stops, a FVP does not back it up by becoming the LAS. Why?
A1-1. Is that FVP running as an LM? Check that the value of
BootOperatFunctionalClass (index 367) is 2 (indicating that it is an LM).
A1-2. Check the values of V(ST) and V(TN) in all LMs on the segment and confirm that
the following condition is met:
Q2. How can I make a FVP become the LAS?
A2-1. Check that the version numbers of the active schedules in the current LAS and
the FVP are the same by reading:
LinkScheduleListCharacteristicsRecord (index 374 for a FVP)
- ActiveScheduleVersion (subindex 3)
A2-2. Make the FVP declare itself as and become the LAS by writing:
❑
0x00 (false) to PrimaryLinkMasterFlagVariable in the current LAS; and
❑
0xFF (true) to PrimaryLinkMasterFlagVariable (index 364) in the FVP.
Q3. On a segment where a FVP works as the LAS, another device cannot be
connected. How come?
A3-1. Check the following bus parameters that indicate the bus parameter as being the
LAS for the FVP and the capabilities of being the LAS for the device that cannot be
connected:
❑
V(ST), V(MID), V(MRD) of FVP: ConfiguredLinkSettingsRecord (index 369)
❑
V(ST), V(MID), V(MRD) of problematic device: DlmeBasicInfo
Then, confirm that the following conditions are met:
A3-2. Check the node address of the problematic device is not included in the
V(FUN)+V(NUN) of the FVP.
FVP
Other LMs
V(ST) X V(TN)
<
V(ST) V(TN)
FVP
Problematic Device
V(ST)
>
V(ST)
V(MID)
>
V(MID)
V(MRD)
>
V(MRD)
Содержание FVP110
Страница 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Страница 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Страница 98: ...FVP 110 Fieldbus Valve Positioner Manual 82 GE Energy Figure 47 Double Acting Actuator Dimensions ...
Страница 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Страница 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 114: ...FVP 110 Fieldbus Valve Positioner Manual 98 GE Energy Table 17 View Object for Transducer Block ...
Страница 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Страница 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Страница 118: ...FVP 110 Fieldbus Valve Positioner Manual 102 GE Energy Table 19 View Object for DI1 DI2 Function Block ...
Страница 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Страница 120: ...FVP 110 Fieldbus Valve Positioner Manual 104 GE Energy Table 21 View Object for PID Function Block ...
Страница 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Страница 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Страница 239: ...223 LM Parameter List Link Master Functions ...
Страница 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Страница 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Страница 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Страница 268: ...FVP 110 Fieldbus Valve Positioner Manual 252 GE Energy Figure 84 Checking Position at Which Clamp Should Be Fixed ...
Страница 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 289: ...273 H Customer Maintenance Parts List ...
Страница 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Страница 291: ......