FVP 110 Fieldbus Valve Positioner Manual
126
GE Energy
Limit Switches
Limit switches monitor whether the valve position has reached a specified high or low limit
position and sends the high limit switch status to channel 2 and the low limit switch status
to channel 3. The thresholds (settings) for the high and low limit switches are set in
LIMSW_HI_LIM and LIMSW_LO_LIM. The switch statuses sent to channels 2 and 3
mean:
❑
0 = off (inactive)
❑
1 = on (active)
Hysteresis of 1% is applied for both High and Low limit switch. While the limit switch of
high side stays ON, it turns to OFF again only when the value of
FINAL_POSITION_VALUE becomes smaller by 1% or less than the value of
LIMSW_HI_LIM. Also, while limit switch of the low side stays ON, it turns to OFF again
only when the value of FINAL_POSITION_VALUE becomes greater by 1% or more than
the value of LIMSW_LO_LIM.
Auto Tuning
WARNING
This function strokes the valve over its full range. Do not
execute while valve is controlling the process. Keep away
from the movable parts to avoid injury.
Auto tuning checks the valve responses and automatically tunes control parameter
settings. The actions performed are chosen as shown in Table 34. To carry out auto
tuning, see “Carrying out Tuning” on page 61. Before carrying out auto tuning, change the
modes of the AO function block and transducer block to O/S.
Table 34
Types of Auto Tuning
Value
Comment
Description
1
Off
—
2
Travel calibration tuning at
stop point
Travel calibration at the tight-shut and full-open positions
3
Control parameter tuning
Tuning of control parameters
4
Travel calibration at stop point
and Control parameter tuning
Sequential execution of travel calibration and control parameter
tuning
5
Cancel execution
Cancellation of auto tuning execution
6
Travel calibration at stop point
without time out (for very large
valve)
Zero-point and span calibration at the tight-shut and full-open
positions without time out
Содержание FVP110
Страница 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Страница 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Страница 98: ...FVP 110 Fieldbus Valve Positioner Manual 82 GE Energy Figure 47 Double Acting Actuator Dimensions ...
Страница 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Страница 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 114: ...FVP 110 Fieldbus Valve Positioner Manual 98 GE Energy Table 17 View Object for Transducer Block ...
Страница 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Страница 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Страница 118: ...FVP 110 Fieldbus Valve Positioner Manual 102 GE Energy Table 19 View Object for DI1 DI2 Function Block ...
Страница 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Страница 120: ...FVP 110 Fieldbus Valve Positioner Manual 104 GE Energy Table 21 View Object for PID Function Block ...
Страница 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Страница 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Страница 239: ...223 LM Parameter List Link Master Functions ...
Страница 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Страница 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Страница 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Страница 268: ...FVP 110 Fieldbus Valve Positioner Manual 252 GE Energy Figure 84 Checking Position at Which Clamp Should Be Fixed ...
Страница 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 289: ...273 H Customer Maintenance Parts List ...
Страница 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Страница 291: ......