Master Programming Level
Programming
GF505 & GF510 Series PN 53164:A 3/26/2007
89
Ademco Contact ID Format - Primary Central Station Phone Number
The information shown in Table 3.3 is automatically programmed for the Primary Central
Station phone number Event Codes when Ademco Contact ID Format is selected. To disable
event reporting, select the desired Event Code to be disabled and press
0
or
Clear
and then
Enter
to disable it. (
Enter
must be pressed to save the selection. Pressing
Escape
will not save
the selection).
Note that disabling the Event Code for the Primary Central Station Phone
Number Event Code will also disable that Event Code for the Secondary Central Station Phone.
Table 3.3 Ademco Contact ID Primary # Event Codes
Event Description
Event Code Settings
Active
Primary # Zone 1 - 10 Alarm
115
Primary # Zone 1 - 10 Disabled
570
Primary # Drill
604
Primary # AC Fault
301
Primary # Zone 1 - 10 Fault
380
Primary # Zone 1 - 10 Dirty
380
Primary # Earth Fault
310
Primary # Low Battery Fault
302
Primary # No Battery Fault
311
Primary # Telco Primary Line Fault
351
Primary # Telco Secondary Line Fault
352
Primary # NAC #1 Fault
321
Primary # NAC #2 Fault
322
Primary # NAC #3 Fault
326
Primary # NAC #4 Fault
327
Primary # NAC #1 Disable
521
Primary # NAC #2 Disable
522
Primary # NAC #3 Disable
526
Primary # NAC #4 Disable
527
Primary # Charger Fault
300
Primary # Comm Trouble Primary #
354
Primary # Comm Trouble Secondary #
354
Primary # Printer Fault
336
Primary # ANN-Bus Fault
330
Primary # Option Card Fault
333
Primary # Memory Fault
304
Future
000
Primary # System Off Normal
308
Primary # System Test Message
602
Primary # System Abnormal Test Message
608