ANN-BUS Devices
Installation
GF505 & GF510 Series PN 53164:A 3/26/2007
43
2.8.6 GFANN-S/PG Serial/Parallel Printer Interface Installation
The GFANN-S/PG Serial/Parallel Printer Interface module allows the ancillary connection of a
serial and/or parallel printer to the FACP for a real-time log of system events, detector status reports
and event history. Proceed with the installation as described in the following:
1. Ensure that all power (AC and DC) has been removed from the FACP.
2. Connect the GFANN-S/PG to the FACP as illustrated in Figure 2.21
3. Using the DIP switches on the back of the GFANN-S/PG module, assign an ID number
(address) to the module
4. Select the address and configuration options for the GFANN-S/PG module as described in
the Programming section of this manual (refer to "ANN-BUS" on page 76)
Note that the Auto-configure feature allows the programmer to quickly bring all installed
ANN-BUS modules online (refer to "Auto-Configure" on page 77)
5. Connect a printer to the GFANN-S/PG Parallel and/or Serial connectors (refer to Figure 2.21
on page 43)
2.8.6.1 Specifications
•
Operating Voltage: 24 VDC
•
Current (Alarm and Standby): 45 mA
•
Ambient Temperature: 32
o
F to 120
o
F (0
o
C to 49
o
C)
•
Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)
•
Mounting: Surface
•
Dimensions: 6”W x 7-3/4”H x 1-7/16”D (15.2 cm W x 19.7 cm H x 3.7 cm D)
•
For indoor use in a dry location only
2.8.6.2 PRN Printer Installation
When connected to the FACP via the GFANN-S/PG module, the PRN prints the status changes
within the control panel and time-stamps the printout with the time of day and date that the
event occurred. It provides 80 columns of data on standard 9” x 11” tractor-feed paper. This
section contains information on connecting a printer to the control panel and setting the printer
options.
Figure 2.21 GFANN-S/PG Connection to FACP
GFANN-S/PG Module
GF505/GF510
Cable
Connectors for
connection to
printer
Parallel
Serial
ANN-BUS and power wiring are
supervised and power-limited
TB3