Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts
NFPA Standard-Specific
GF505 & GF510 Series PN 53164:A 3/26/2007
137
B.1 Central Station/Remote Station Transmitter:
Connection to FACP Dry Contacts
The dry contacts of the FACP programmable relays can be used to trip a UL-864 Listed Central
Station/Remote Station Transmitter. The FACP contacts must be supervised by the Central Station/
Remote Station Transmitter module using End-of-Line Resistors (ELRs) with a value determined
by the Transmitter manufacturer. Power is also provided by the Central Station/Remote Station
Transmitter manufacturer. Refer to the Central Station/Remote Station Transmitter manufacturer’s
manual for details.
Figure B.5 FACP Dry Contacts Connection to Central Station/Remote Station Transmitter
Typical Central Station/Remote Station Transmitter Module
Typical Input Zone Triggers
Fire Alarm Control Panel
Al
ar
m
Superv
.
T
ro
ubl
e*
*Note: The Trouble Relay is a
fail-safe relay. With power
applied to the FACP and no
troubles in the panel, the wiring
should be connected to the NO
and C contacts as indicated in the
illustration.