Installation
ANN-BUS Devices
50
GF505 & GF510 Series PN 53164:A 3/26/2007
2.8.9 GFANN-RLY Relay Module
The GFANN-RLY relay module provides 10 programmable Form-C relays when used with a
compatible FACP.
2.8.9.1 GFANN-RLY Board Layout
Figure 2.27 illustrates the GFANN-RLY board showing locations of screw terminals for
connection to the FACP and the DIP switches for selecting the ANN-BUS ID number.
2.8.9.2 Specifications
•
Operating Voltage: 24 VDC
•
Max. Current:
Alarm: 75 mA
Standby: 15 mA
•
Relay Contact Ratings:
2 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
•
Operating Temperature: 32
o
F to 120
o
F (0
o
C to 49
o
C)
•
For indoor use in a dry location only
2.8.9.3 Mounting/Installation
The GFANN-RLY relay module can be mounted inside the FACP main circuit board chassis.
ANN-BUS (ID#)
Address DIP switch
ANN-BUS Connector
Figure 2.27 GFANN-RLY Board Layout