SECTION 1
Product Description
The GF505 is a five zone FACP (Fire Alarm Control Panel) and the GF510 is a ten zone FACP.
The information in this manual refers to both the GF505 and GF510 unless otherwise specified.
The combination control and digital communicator panels provide reliable fire signaling protection
for small to medium sized commercial, industrial and institutional buildings. The FACP is
compatible with System Sensor’s I
3
detectors which are conventional smoke detectors that can
transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a
supervisory ‘freeze’ signal when the ambient temperature falls below the detector rating of
approximately 45
o
F (refer to System Sensor I
3
Installation and Maintenance Instructions). In
addition, the control panel is compatible with conventional input devices such as two-wire smoke
detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other
normally-open contact devices. Refer to Gamewell-FCI Device Compatibility Document for a
complete listing of compatible devices.
Outputs include four NACs (Notification Appliance Circuits), three programmable Form-C relays
(factory programmed for Alarm, Trouble and Supervisory) and 24 VDC special application
resettable and nonresettable power outputs. The FACP supervises all wiring, AC voltage, battery
level and telephone line integrity.
Activation of a compatible smoke detector or any normally-open fire alarm initiating device will
activate audible and visual signaling devices, illuminate an indicating LED, display alarm
information on the panel’s LCD, sound the piezo sounder at the FACP, activate the FACP alarm
relay and operate an optional module used to notify a remote station or initiate an auxiliary control
function.
The following versions of the GF505/GF510 are available:
Note: Unless otherwise specified, the information in this manual applies to all versions of the
panels.
1.1 Product Features
•
Built-in DACT (Digital Alarm Communicator/Transmitter)
•
Style B (Class B) IDC (Initiating Device Circuit)
GF505 - five programmable IDCs
GF510 - ten programmable IDCs
•
Four Style Y (Class B) NAC (Notification Appliance
Circuit) - special application power
•
Three programmable Form-C relays
•
Built-in Programmer
•
Touchtone/Rotary dialing
•
Programmable Make/Break Ratio
•
Optional Dress Panel DP-51050 (red) or DP-51050W (white)
•
Optional Dress Panel DP-51050LED or DP-51050LEDW (white): includes a GFANN-LED
Annunciator module
•
Optional Trim Ring TR-CE (red) or TR-CEW (white) for semi-flush mounting the cabinet
•
ANN-BUS for connection to optional:
FACP Version
Description
GF505
Five Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current
GF510
Ten Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current