Programming
Maintenance Programming Level
100
GF505 & GF510 Series PN 53164:A 3/26/2007
Pressing
1
while viewing the History screen will cause the following screen to be displayed:
To view all the events which have occurred in the control panel since the history file was last
erased, press
1
while viewing the Events screen. To view only alarms which have occurred, press
2
while viewing the Events screen. To view events other than alarms, press
3
. The most recent event
will be displayed on the screen. To view all of the selected events, press the up or down arrow keys
to scroll through the list of events. If no events have occurred, the display will read
NO EVENTS
IN HISTORY
.
Pressing 2 while viewing the History Screen will cause the following screen to be displayed:
Pressing
1
while viewing the Erase History Screen will cause the message
ERASING HISTORY,
PLEASE WAIT
to be displayed. The display will then return to the History Screen. Pressing
2
will
cause the display to return to the History Screen without erasing the History file.
3.6.3 Walktest
To perform a walktest, press
3
while viewing Maintenance Screen #1. The following screen will be
displayed:
The operator can press
1
to perform a silent walktest or
2
to perform an audible walktest. The
display will read
UNIT IN WALKTEST
. To end the Walktest, press the Esc (Escape) key.
Pressing
3
after the walktest has been completed, will allow the operator to view the results of the
walktest.
HISTORY
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
ERASE HISTORY
PROCEED ?
1=YES 2=NO
Erase History Screen
PROGRAMMING
1=INPUT ZONES
2=HISTORY
3=WALKTEST
Maintenance Screen #1
WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW RESULT