Installation
ANN-BUS Devices
48
GF505 & GF510 Series PN 53164:A 3/26/2007
2.8.8 GFANN-LED Annunciator Module
The GFANN-LED annunciator module provides LED annunciation of general system faults and
input zones/points when used with a compatible FACP. The GFANN-LED module provides alarm
(red), trouble (yellow) and supervisory (yellow) indication for up to ten input zones or addressable
points.
2.8.8.1 GFANN-LED Board Layout
Figure 2.25 illustrates the GFANN-LED board showing locations of screw terminals for
connection to the FACP and the DIP switches for selecting the ANN-BUS ID number.
2.8.8.2 Specifications
•
Max. ANN-BUS Voltage: 24 VDC
•
Max. Current:
Alarm: 68 mA
Standby: 28 mA
•
Operating Temperature: 32
o
F to 120
o
F (0
o
C to 49
o
C)
•
For indoor use in a dry location only
2.8.8.3 Mounting/Installation
The GFANN-LED Module is supplied mounted to the DP-51050LED/W Dress Panel. Install
the dress panel as described in the documentation supplied with the DP-51050LED.
ANN-BUS (ID#)
Address DIP switch
ANN-BUS Connector
Figure 2.25 GFANN-LED Board Layout