Specifications
Product Description
GF505 & GF510 Series PN 53164:A 3/26/2007
13
GFANN-80 Remote LCD Annunciator
GFANN-I/O LED Driver
GFANN-S/PG Printer Module
GFANN-RLY Relay Module
GFANN-LED Annunciator Module
•
80-character LCD display (backlit)
•
Real-time clock/calendar with daylight savings time control
•
History log with 256 event storage
•
Control Buttons
ACK (Acknowledge)
Alarm Silence
System Reset/Lamp Test
Drill
•
LED Indicators
Fire Alarm
Supervisory
Trouble
AC Power
Alarm Silence
Primary and Secondary Phone Line Active LEDs
•
Piezo sounder for alarm, trouble and supervisory
•
24 volt operation
•
Low AC voltage sense
•
Alarm Verification
•
NACs Programmable for:
Silence Inhibit
Auto-Silence
Strobe Synchronization (System Sensor, Wheelock, Gentex, Faraday, Amseco)
Selective Silence (horn-strobe mute)
Temporal or Steady Signal
Silenceable or Nonsilenceable
•
Automatic battery charger with charger supervision
•
Silent or audible walktest capabilities
•
Optional CAC-5X Class A Converter Module for NACs and IDCs
•
Optional 4XTMF Transmitter Module
1.2 Specifications
AC Power
GF505 & GF510 (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.80 amps
Wire size: minimum #14 AWG (2.0 mm
2
) with 600V insulation
Supervised, nonpower-limited
Battery (sealed lead acid only) - J12
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 1.4 amp
Supervised, nonpower-limited
Maximum Charger Capacity: 26 Amp Hour battery for GF505 & GF510 [two 18 Amp Hour
batteries can be housed in the FACP cabinet.]
Minimum Battery Size: 7 Amp Hour
Initiating Device Circuits - TB4 (and TB6 on GF510 only)
Alarm Zones 1 - 5 on TB 4 (GF505)