Programming
Master Programming Level
90
GF505 & GF510 Series PN 53164:A 3/26/2007
Ademco Contact ID Format - Secondary Central Station Phone Number
The information shown in Table 3.4 is automatically programmed for the Secondary Central
Station phone number Event Codes when Ademco Contact ID Format is selected. To disable
event reporting, select the desired Event Code to be disabled and press
0
or
Clear
and then
Enter
to disable it. (
Enter
must be pressed to save the selection. Pressing
Escape
will not save
the selection).
Note that disabling the Event Code for the Primary Central Station Phone
Number Event Code will also disable that Event Code for the Secondary Central Station Phone.
Table 3.4 Ademco Contact ID Secondary # Event Codes
Event Description
Event Code Settings
Active
Secondary # Zone 1 - 10 Alarm
115
Secondary # Zone 1 - 10 Disabled
570
Secondary # Drill
604
Secondary # AC Fault
301
Secondary # Zone 1 - 10 Fault
380
Secondary # Zone 1 - 10 Dirty
380
Secondary # Earth Fault
310
Secondary # Low Battery Fault
302
Secondary # No Battery Fault
311
Secondary # Telco Primary Line Fault
351
Secondary # Telco Secondary Line Fault
352
Secondary # NAC #1 Fault
321
Secondary # NAC #2 Fault
322
Secondary # NAC #3 Fault
326
Secondary # NAC #4 Fault
327
Secondary # NAC #1 Disable
521
Secondary # NAC #2 Disable
522
Secondary # NAC #3 Disable
526
Secondary # NAC #4 Disable
527
Secondary # Charger Fault
300
Secondary # Comm Trouble Primary #
354
Secondary # Comm Trouble Secondary #
354
Secondary # Printer Fault
336
Secondary # ANN-BUS Fault
330
Secondary # Option Card Fault
331
Secondary # Memory Fault
304
Future
000
Secondary # System Off Normal
308
Secondary # System Test Message
602
Secondary # System Abnormal Test Message
608