![Gamewell GF505 Series Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/gamewell/gf505-series/gf505-series_installation-programming-and-operation-manual_3357398015.webp)
Controls and Indicators
Product Description
GF505 & GF510 Series PN 53164:A 3/26/2007
15
Form-C Relays - Programmable - TB8
Relay 1 (factory default programmed as Alarm Relay)
Relay 2 (factory default programmed as fail-safe Trouble Relay)
Relay 3 (factory default programmed as Supervisory Relay)
Relay Contact Ratings: 2 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Special Application Resettable Power - TB9
Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA - appropriate for powering 4-wire smoke detectors (see
note 1)
Power-limited Circuitry
Refer to Gamewell-FCI Device Compatibility Document for compatible listed devices
Special Application Resettable or Nonresettable Power - TB9
Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA (see note 1)
Power-limited Circuitry
Jumper selectable by JP31 for resettable or nonresettable power:
Jumper pins 1 & 2 on JP31 for nonresettable power
Jumper pins 2 & 3 on JP31 for resettable power
Refer to Gamewell-FCI Device Compatibility Document for compatible listed devices
Remote Sync Output - TB2
24 VDC nominal special application power
Maximum current is 40 mA
End-of-Line Resistor: 4.7K
Ω
Supervised and power-limited circuit
Auxiliary Trouble Input - J6
The Auxiliary Trouble Input is an open collector circuit which can be used to monitor an
external device for trouble conditions. It can be connected to the trouble bus of a peripheral,
such as a power supply, which is compatible with open collector circuits.
All connections must be in conduit, less than 20 ft. (610 cm) in length in the same room.
1.3 Controls and Indicators
LCD Display
The FACP uses an 80-character
(4 lines X 20 characters) high viewing angle
LCD display. The display includes a long life
LED backlight that remains illuminated. If AC
power is lost and the system is not in alarm, the
LED backlight will turn off to conserve batteries.
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED
indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25
keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
SYSTEM ALL NORMAL
10:00A 012105