Installation
Power-limited Wiring Requirements
30
GF505 & GF510 Series PN 53164:A 3/26/2007
2.5 Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower-
limited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must
enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram is
illustrated below.
Figure 2.11 Typical UL Power-limited Wiring Requirements
Power-limited Circuits (Class 2)
Power-limited Circuits (Class 2)
Power-limited
Circuits
(Class 2)
Nonpower-
limited
Circuit
AC Power
120 VAC
Hot (L1)
Ground
Neutral (L2)
CAC-5X
5udULw
ir
e.cdr
4XTMF
earth
ground
Nonpower-
limited
Circuit
Power-limited
Circuit
(Class 2)
GF505 FACP