Master Programming Level
Programming
GF505 & GF510 Series PN 53164:A 3/26/2007
87
Communication Format
Pressing
1
while viewing Primary/Secondary Screen #3 will cause the following screen to be
displayed:
The Communication Format is determined by the type of receiver that the DACT is transmitting
to.
Consult your Central Station for proper selection or consult our factory representatives.
For any format chosen, the control panel automatically programs all of the event codes.
Select the Communication Format by pressing the corresponding number key while viewing the
Comm Format screen. The following table describes each format:
Event Codes
Pressing
1
while viewing Primary/Secondary Screen #4 will cause the following screen to be
displayed:
Pressing the down arrow key allows viewing of all Events associated with the selected
Communication Format. Pressing the number corresponding to the event displayed in each
screen will display its default active and restoral event codes which can be customized by the
programmer.
For example, if Ademco Contact ID is the selected format, pressing
3
for Zone 3 Alarm will
display the following screen which allows the Event Code to be changed from the default value.
Table 3.1 Communication Formats
Screen Selection
Communication Format Description
ADEMCO CONTACT ID
Contact ID, DTMF, 1400/2300 ACK
SIA-DCS-8
Security Industry Association, 8 messages per call
SIA-DCS-20
Security Industry Association, 20 messages per call
CENTRAL STATION
1=COMM FORMAT
Primary/Secondary Screen #3
COMM FORMAT
1=ADEMCO CONTACT ID
2=SIA-DCS-8
3=SIA-DCS-20
CENTRAL STATION
1=EVENT CODES
Primary/Secondary Screen #4
EVENT CODES
1=ZONE 1 ALARM
2=ZONE 2 ALARM
3=ZONE 3 ALARM
Event Code Screen
ZONE 3 ACTIVE
115