Installation
ANN-BUS Devices
44
GF505 & GF510 Series PN 53164:A 3/26/2007
2.8.6.2.1 Connecting PRN Printer
Remote printers require a primary AC power source. If required for the fire alarm system
configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a
secondary power source (battery backup). Since a secondary power source is not provided as a
standard feature, a separate UL-listed Uninterruptible Power Supply (UPS) should be used.
The building emergency power supply may be used, as long as it meets the power continuity
requirements of NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the GFANN-S/PG module using a standard DB-25
cable. One end of the cable will plug into the DB-25 connector on the PRN printer and the
other end plugs into the parallel connector on the GFANN-S/PG module. Note that the 9-pin
DB-9 port on the GFANN-S/PG is used to connect a serial printer. The 25-pin port is used for a
Centronics parallel printer cable. Connect either a serial or parallel printer, but not both at the
same time.
2.8.6.2.2 Setting Printer Options
Refer to the documentation supplied with the PRN printer for instructions on using the printer
menu controls. Set the printer options (under the menu area) as shown in the following table:
Table 2.2 PRN Setup Options
Option
Setting
Option
Setting
Font
HS Draft
CPI
10CPI
LPI
6 LPI
Skip
0.5
ESC Character
ESC
Emulate
Epson FX-850
Bidirectional Copy
ON
I/O
CG-TAB
Graphic
Buffer
40K
Country
E-US ASCII
Serial
Auto CR
OFF
Baud
9600 or 2400
Color Option
Not Installed
Format
7 Bit, Even, 1 Stop
Formien
Protocol
XON/XOFF
Lines
6LPI=60
Character Set
Standard
Standard
Exec 10.5
SI.Zero
On
Auto LF
On
PAPER
BIN 1
12/72”
BIN 2
12/72”
SINGLE
12/72”
PUSH TRA
12/72”
PULL TRA
12/72”
PAP ROLL
12/72”