![Gamewell GF505 Series Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/gamewell/gf505-series/gf505-series_installation-programming-and-operation-manual_3357398017.webp)
Digital Alarm Communicator/Transmitter
Product Description
GF505 & GF510 Series PN 53164:A 3/26/2007
17
1.4 Digital Alarm Communicator/Transmitter
Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1
for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs
are provided as well as a green
Kissoff
LED. The integral digital communicator provides the
following functions:
•
Line Seizure: takes control of the phone lines disconnecting any premises phones
•
Off/On Hook: performs on and off-hook status to the phone lines
•
Listen for dial tone: 440 Hz tone typical in most networks
•
Dialing the Central Station(s) number: default is Touch-Tone
®
, programmable to rotary
•
For tone burst or touchtone type formats: discern proper
Ack
and
Kissoff
tone(s). The
frequency and time duration of the tone(s) varies with the transmission format. The control
panel will adjust accordingly.
•
Communicate in the following formats:
Ademco Contact ID
SIA-DCS-8
SIA-DCS-20
1.5 Components
Main Circuit Board
The main circuit board contains the system’s CPU, DACT and other primary components and
wiring interface connectors. Optional modules plug in and are mounted to the main circuit board.
Power Supply
One power supply is provided standard with each FACP, mounted to a chassis.
•
FLPS-7 for the GF505 & GF510
Cabinet
The backbox measures 16.65” (42.29 cm) x 19.0” (48.26 cm) x 5.207” (13.23 cm) and provides
space for two batteries (up to 18 Amp Hours). Also available are an optional dress panel (DP-
51050/W) which mounts inside the cabinet and trim-ring (TR-CE/W).
Batteries
The cabinet provides space for two 18 Amp Hour batteries. Batteries must be ordered separately.
1.6 Optional Modules and Accessories
CAC-5X Class A Converter Module
The CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits to
Style D (Class A) and Style Y (Class B) Notification Appliance Circuits to Style Z (Class A). The
module connects to J2 on the GF505 and to J7 on the GF510. Note that two Class A Converter
modules are required for the 10 zone panel.
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and
trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper
option allows the reverse polarity circuit to open with a system trouble condition if no alarm
condition exists. The 4XTMF mounts to the main circuit board connectors J4 & J5.
GFANN-80 LCD Annunciator
The GFANN-80 is a remote LCD annunciator which mimics the information displayed on the