FACP with Keltron
Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts
138
GF505 & GF510 Series PN 53164:A 3/26/2007
APPENDIX C
FACP with Keltron
The following figure illustrates the connections between the FACP and Keltron Receiver/
Transmitter.
CAUTION!
For reasons of wiring diagram clarity, terminal designations of Keltron modules are
not shown in actual order. Follow Keltron manual and module markings for exact terminal
locations to prevent severe module damage!
IMPORTANT!
All connections between the FACP and Keltron modules must be made within 20
feet and enclosed within conduit or equivalently protected against mechanical injury.
Fire Alarm Control Panel
(terminal blocks are not shown in
their actual positions in order to
clarify wiring connections)
Keltron 95M3158 TTM-RPS
1. Terminals 7 and 8: Remote station alarm/trouble inputs.
2. Terminals 9 and 10: Sprinkler supervisory input.
Note:
Cut TBL jumper on 4XTMF module to send
alarm/trouble signal from the same pair or terminals.
Alarm/Trouble Signal
Sprinkler Supervisory Signal
*Note:
For more information,
refer to Keltron manual.
4XTMF Module