Programming
User Programming
52
GF505 & GF510 Series PN 53164:A 3/26/2007
SECTION 3
Programming
3.1 User Programming
The GF505/GF510 FACP is completely field programmable using the panel keypad and requires
no special software skills.
While programming the FACP, the fire protection capabilities of the
control panel are enabled.
Site-specific programming may be accomplished:
•
Manual programming or editing, using the FACP keypad
The
System All Normal
screen will be displayed in a programmed system with no active alarms,
troubles or supervisories, as illustrated below:
Read Status mode can be entered while the panel is in any mode of operation. If an alarm or
supervisory event exists at the panel, the event must be cleared before entering Programming mode.
To access any of the programming or read status features, the
Enter
or
Mode
key must be pressed,
which will cause the LCD to display the following:
Pressing
1
, while this screen is being displayed, will cause the control panel to enter the Read
Status Mode which allows the user to view the programmed features and status of the control panel
The Read Status feature is not password protected. Refer to "Read Status" on page 112 for a
detailed description of this feature.
Pressing
2
will select user Programming Mode which may only be accomplished by an authorized
person. After pressing
2
, a screen will prompt for a password. After entering the correct password,
the user may select from a list of programming options.
Exit Programming and Read Status Mode
The programmer can exit any mode by repeatedly pressing the keypad
ESC
(Escape) key until the
display reads System All Normal.
Note that the data which is entered during Programming mode
is not saved until the programmer exits this mode by repeatedly pressing the ‘ESC’ key. If the Reset
key is pressed or power is lost before exiting Programming mode, all data just entered will be lost
.
!!!
SYSTEM ALL NORMAL
10:00A 070707
1=READ STATUS MODE
2=PROGRAMMING MODE
See Page