Programming
Master Programming Level
88
GF505 & GF510 Series PN 53164:A 3/26/2007
The following table lists the Zone Alarm Types that can be programmed for zones 1 through 10
and the corresponding Event Codes for Ademco Contact ID and SIA DCS Formats. Note that
Table 3.3 on page 89, Table 3.4 on page 90, Table 3.5 on page 91 and Table 3.6 on page 93 list
the default settings for Zone 1 through Zone 10. These can be changed to any of the Types
listed in Table 3.2 .
Note: The third character in the SIA-DCS Format (
x
in the table below) represents the zone
number.
The following tables list all of the Events and their default Event Codes for the Ademco Contact
ID and SIA-DCS Communication Formats.
Note: A detector
freeze
condition will be reported as a Supervisory Event Code.
Table 3.2 Zone Alarm Type Event Codes
Zone Alarm Type
Ademco Contact ID
SIA-DCS Format
Active
Active
Restoral
Pull-Station
115
FAx
FHx
Waterflow
113
SAx
SHx
Waterflow Nonsilenceable
113
SAx
SHx
Combo
113
SAx
SHx
Combo AutoResettable Supervisory
113
SAx
SHx
2-Wire Detector
111
FAx
FHx
Normally Open Contact
110
UAx
UHx
Fire
110
FAx
FHx
Tamper
144
TAx
THx
Supervisory
200
FSx
FVx
Supervisory AutoResettable
200
FSx
FVx
Medic-Alert 100
MAx
MHx
Hazard-Alert
150
PAx
PHx
Tornado-Alert
150
PAx
PHx
Proc-Mon
200
IAx
IRx
Procmon-AR
200
IAx
IRx
AC-Loss-Mon
301
ATx
ARx
Drill-Switch
604
FIx
FKx
Drill-Switch AutoResettable
604
FIx
FKx