Programming
Master Programming Level
58
GF505 & GF510 Series PN 53164:A 3/26/2007
Pressing the down arrow key will display additional zone types as indicated in the following
table.
While viewing any Zone Type screen, select the type of zone being programmed by pressing the
corresponding keyboard number key. The display will return to Edit Input Zone Screen #2 and
indicate the selection next to the Type option.
Verification
Alarm verification is used to confirm that a smoke detector activation is a true alarm condition
and not a false alarm. This feature is selected by pressing
3
while viewing the Edit Zone Screen
#2 so that the display reads
Verification On
. Each time the
3
key is pressed, the display will
toggle between
Verification On
and
Verification Off
. For a detailed description, refer to "Alarm
Verification (None or One Minute)" on page 111.
Note that verification can only be enabled for a zone that is programmed as a smoke detector
type. Zones programmed for any other type will not allow the Verification feature to be
enabled.
Do not use the verification feature if a mix of smoke detectors and normally open
contact devices are connected to the same zone
.
Zone Type
Action When Activated
Pull-Station
Fire Alarm
Waterflow
Fire Alarm Delayed (uses waterflow delay)
Waterflow Nonsilenceable
Fire Alarm (uses waterflow delay)
Combo
Fire/Supervisory (uses waterflow delay)
Combo AutoResettable Supervisory
Fire/Supervisory AR, nonlatching (uses waterflow delay)
2-Wire Detector
Fire Alarm
Normally Open Contact
Fire Alarm
Fire
Fire Alarm
Tamper
Supervisory
Supervisory
Supervisory, latching
Supervisory AutoResettable
Supervisory, nonlatching
Medic-Alert Supervisory,
latching
Hazard-Alert
Supervisory, latching
Tornado-Alert
Supervisory, latching
Proc-Mon
Piezo
Procmon-AR
Piezo, nonlatching
AC-Loss-Mon
Trouble
Ack-Switch
Acts like panel Acknowledge Key
Sil-Switch
Acts like panel Alarm Silence Key
Drill-Switch
Acts like panel Drill Key
Reset-Switch
Acts like panel Reset Key
PAS-Bypass
Positive Alarm Sequence Disable
Drill-Switch AutoResettable
Acts like panel Drill Key, nonlatching
INPUT ZONE
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Input Zone Screen #2
See Page